System
The Kingspan
Building Management Systems
Building Management Systems include sensors / controllers that may need to be
installed inside/outside the ductwork to monitor temperature, pressure and other
parameter of the HVAC system.
These sensors / controllers typically have a mounting plate with mounting holes
and are fixed to steel ductwork using screws.
A hole is also drilled into the ductwork to allow the insertion of the measuring
probe.
With ductwork fabricated from the KoolDuct system, a protective metal plate
needs to be installed inside the ductwork using adhesive/sealant before the
sensor / controller is fixed to the outside KoolDuct ductwork wall, so that the
insulating panel is protected by the sandwich type of installation - mounting plate
outside KoolDuct, metal plate inside KoolDuct.
Once the protective metal plate is installed, standard fixing operation can follow
(e.g. drilling, fixing screws).
In case the sensor / controller needs to be installed after the duct is already in
place, an access door will be required on KoolDuct, to allow the above mentioned
installation.