The Kingspan
7
KoolDuct
/
" (R-6) - Schedule of Duct Reinforcement
8
Tiger Clip Coupling
Max Duct
Duct Dimension
segment
length
4 - 8
154 3/4"
9 - 12
154 3/4"
13 - 16
154 3/4"
19 - 20
154 3/4"
21 - 24
154 3/4"
25 - 28
154 3/4"
29 - 32
154 3/4"
33 - 36
154 3/4"
37 - 40
154 3/4"
41 - 45
154 3/4"
46 - 48
47 1/4"
49 - 52
47 1/4"
53 - 56
47 1/4"
57 - 60
47 1/4"
61 - 64
47 1/4"
65 - 68
47 1/4"
69 - 72
47 1/4"
73 - 76
47 1/4"
79 - 80
47 1/4"
Over 2000
NOTES
1@Joint
Reinforcing Bars shall be placed at Joint only, and
Tiger Clip: Reinfoircing bar at MAX 12" FROM JOINT, on both sides of the joint
1@36"
Reinforcing Bars shall be placed at a maximum of 36" centers, and
Tiger Clip: FIRST and LAST bar at MAX 12" FROM JOINT
1@24"
Reinforcing Bars shall be placed at a maximum of 24" centers, and
Tiger Clip: FIRST and LAST bar at MAX 12" FROM JOINT
Static Pressure Positive and Negative
1/2 in.w.g.
1 in.w.g.
NO REINFORCEMENT
1@Joint
1@Joint
1@Joint
1@Joint
1@Joint
1@Joint
1@36"
1@Joint
1@36"
1@24"
1@24"
1@24"
1@24"
1@24"
1@24"
1@24"
1@24"
System
2 in.w.g.
3 in.w.g.
NOT APPLICABLE
1@Joint
1@Joint
1@36"
1@36"
1@36"
1@36"
NOT APPLICABLE
Pos Pressure
only
4 in.w.g.
73