E2S BExCTS110-05 Instruction Manual

E2S BExCTS110-05 Instruction Manual

Combined sounder / beacon with call relay for use in flammable gas and dust atmospheres

Advertisement

Quick Links

1) Warnings
 DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
 DO NOT OPEN WHEN ENERGIZED
 POTENTIAL ELECTROSTATIC CHARGING
HAZARD – CLEAN ONLY WITH A DAMP
CLOTH
 COVER BOLTS CLASS A4-80
 USE HEAT RESISTING CABLES AND CABLE
GLANDS (RATED 110°C) AT AMB.
TEMPERATURES OVER 40°C
2) Rating & Marking Information
All units have a rating label, which carries the following
important information: -
Model No.:
BExCTS110-05D-P or BExCTS110-05D-R-P
Input Voltage: DC Units
AC Units
BExCTS110-05D-P or BExCTS110-05D-R-P Codes:
Ex db IIB T5 Gb Ta. -50°C to +40°C
Ex db IIB T4 Gb Ta. -50°C to +70°C
Ex tb IIIC T110°C Db Ta. -50°C to +55°C
Ex tb IIIC T125°C Db Ta. -50°C to +70°C
Certificate No. KEMA 01ATEX2223X
IECEx KEM 10.0025X
Epsilon x
Equipment Group and
Category:
CE Marking
Notified Body No.
_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document No. D210-00-681-IS
INSTRUCTION MANUAL (ATEX / IECEx)
BExCTS110-05D-P and BExCTS110-05D-R-P Combined
Sounder / Beacon with Call Relay For use in Flammable Gas
BExCTS110-05D-P
12V or 24V or 48V
115V or 230V
II 2G
II 2D
2813
Issue 3
20-04-2020
and Dust Atmospheres
The units can be installed in locations with the following
conditions:
Area Classification Gas:
Explosive gas air mixture likely to occur in
Zone 1
normal operation.
Explosive gas atmosphere not likely to
Zone 2
occur in normal operation but may be
present for short periods.
Gas Groupings:
Group IIA
Propane
Group IIB
Ethylene
Temperature Classification:
T1
450ºC
T2
300ºC
T3
200ºC
T4
135ºC
T5
100ºC (up to 40°C ambient)
Area Classification Dust:
Explosive dust air mixture likely to occur in
Zone 21
normal operation.
Explosive dust air mixture not likely to
Zone 22
occur in normal operation, and if it does, it
will only exist for a short time.
Dust Groupings:
Group IIIA
Combustible Dusts
Group IIIB
Non-Conductive Dust
Group IIIC
Conductive Dust
Maximum Surface Temperature for Dust Applications:
110ºC at +55 ºC ambient
125 ºC at +70 ºC ambient
IP Rating:
IP66/67 to EN/IEC60529 and IP6X to
EN/IEC60079-0, EN/IEC60079-31
Equipment Category:
Equipment Protection Level:
Ambient Temperature Range:
-50°C to +70°C Gas Groups IIA and IIB
-50°C to +70°C Dust Groups IIIA, IIIB and IIIC
sales@e-2-s.com
www.e-2-s.com
Sheet 1 of 8
BExCTS110-05D-R-P
2G / 2D
Gb / Db
Tel: +44 (0)208 743 8880
Fax: +44 (0)208 740 4200

Advertisement

loading

Summary of Contents for E2S BExCTS110-05

  • Page 1 INSTRUCTION MANUAL (ATEX / IECEx) BExCTS110-05D-P and BExCTS110-05D-R-P Combined Sounder / Beacon with Call Relay For use in Flammable Gas and Dust Atmospheres BExCTS110-05D-R-P BExCTS110-05D-P 1) Warnings The units can be installed in locations with the following  DO NOT OPEN WHEN AN EXPLOSIVE conditions: ATMOSPHERE IS PRESENT ...
  • Page 2 adjustment screws on the side of the unit must be fully 3) Type Approval Standards tightened to ensure that the unit cannot move in service. The combined sounder beacon carries an EC Type Examination Certificate and IECEx Certificate of Conformity, and have been certified to comply with the following standards: EN60079-0:2012 + A11 and EN IEC 60079-0 :2018 /...
  • Page 3: Power Supply Selection

    M20 entries and labels on the same side). Carefully push the For use in explosive dust atmospheres, a minimum ingress cover in place allowing time for the air to be expelled. Only protection rating of IP6X must be maintained. after the cover is fully in place should the four M6 Stainless The BEx combined sounder beacon range can be supplied Steel A4-80 cover bolts and their spring washer be inserted with the following types of adapters:...
  • Page 4 way, the sum of the 2-off wires must be a maximum cross Fig. 5a Sounder AC Terminals sectional area of 2.5mm². Strip wires to 8mm. Wires may also be fitted using ferrules. Terminal screws need to be tightened Interconnecting Terminals down with a tightening torque of 0.45 Nm / 5 Lb-in.
  • Page 5 The Telephone Selection Table on page seven shows the switch positions 1 - 4 for the country setting and switch 5 for TB2 Beacon TB3 Sounder the beacon continuous or pulse mode and switch 6 for the Mains Supply Mains Supply sounder continuous or pulse mode.
  • Page 6: Maintenance, Overhaul & Repair

    MUST be in the order shown in figure 11. operation, take care when handling the equipment. M5x16 Hex Socket Screw The beacon cover is interchangeable, contact E2S Ltd for a M5 Spring Washer replacement cover available in various colours. M5 Plain Washer To change the cover, unscrew the M5 socket head screws and remove the M5 screws, M5 spring &...
  • Page 7 DIP Switch DIP Switch Telephone Selection Settings Settings Settings Dialing Country Setting 2 3 4 Australia 0 0 0 Ireland New Zealand Singapore South Africa Belgium 0 0 0 Canada Cyprus Hong Kong Spain Turkey Czech Republic 1 0 0 Finland France Germany...
  • Page 8 Tone Selection DIP Switch Stage Selection Settings Stage 1 Frequency Description 2 3 4 5 Stage 2 Stage 3 Continuous 1000Hz Toxic Gas Alarm 0 0 0 0 Tone 31 Tone 11 Alternating 800/1000Hz at 0.25s intervals 0 0 0 0 Tone 17 Tone 5 Slow Whoop 500/1200Hz at 0.3Hz with 0.5s gap repeated...