Viking HORIZON MIRAGE B-1 Technical Data
Viking HORIZON MIRAGE B-1 Technical Data

Viking HORIZON MIRAGE B-1 Technical Data

Extended coverage 20 ft x 20 ft (6,1 m x 6,1 m) concealed sprinklers

Advertisement

Quick Links

February 11, 1999
1. PRODUCT NAME
®
VIKING HORIZON
MIRAGE
TENDED COVERAGE CONCEALED
PENDENT SPRINKLERS
Model B-1 Standard Orifice Sprinkler
Base Part No. 08498
Available since 1993
Model B-2 Large Orifice Sprinklers
Base Part No. 10485
Available since 1998
Base Part No. 10680
Available since 1999
Cover Plate Assembly
Base Part No. 09804
Available since 1996
2. MANUFACTURER
THE VIKING CORPORATION
210 N. Industrial Park Road
Hastings, Michigan 49058 U.S.A.
Telephone:
(616) 945-9501
(877) 384-5464
Fax:
(616) 945-9599
e-mail: techsvcs@vikingcorp.com
3. PRODUCT DESCRIPTION
Viking Extended Coverage Horizon
®
rage
Concealed Sprinklers are small,
solder link and lever spray sprinklers
designed for installation on concealed
pipe systems.
Equipped with a special deflector, the
sprinklers are designed to meet Light
Hazard density requirements for specific
extended areas of coverage when the
required minimum water supply is pro-
vided at the sprinkler.
After the sprinkler system has been
tested and the ceiling finish applied, the
sprinkler is hidden from view by a low
profile, small-diameter cover plate, in-
stalled flush to the ceiling. The cover
plate is available in several decorative
finishes to meet design requirements.
The "push on", "thread off" design al
lows for easy installation of the cover
plate, with up to 1/2" (12,7 mm) of
vertical adjustment. The "thread off" fea-
ture is designed to prevent unwanted
disengagement of the cover assembly.
The cover assembly can be removed
and reinstalled to permit temporary re-
moval of ceiling panels without taking
the sprinkler system out of service and
removing the sprinkler.
Inside the body of the sprinkler, the de-
flector and sealing assembly are held in
position by a heat-sensitive fusible link.
The sprinklers are listed as standard
response sprinklers when installed
according to the listed 20 ft. x 20 ft.
(6,1 m x 6,1 m) spacing. (Refer to the
approval chart on this page for other
listings.)
Note: Units of measure in parentheses may be approximations.
Form No. F_061593
TECHNICAL DATA
®
EX-
For Light Hazard Occupancies only.
Viking Horizon
Extended Coverage
Concealed Sprinkler
Figure A
Sprinkler
Temperature
Classification
Ordinary
®
Mi-
Sprinkler NPT
Part
Thread of Coverage
3
Number
Size
1/2"
08498
(15 mm) 4,9 m x 4,9 m
1/2"
08498
(15 mm) 5,5 m x 5,5 m
1/2"
08498
(15 mm) 6,1 m x 6,1 m
Sprinkler
NPT
Thread
Part
3
Numbers
Size
10485
1/2" (15 mm) 16 ft. x 16 ft.
10680
3/4" (20 mm) 4,9 m x 4,9 m
10485
1/2" (15 mm) 18 ft. x 18 ft.
10680
3/4" (20 mm) 5,5 m x 5,5 m
10485
1/2" (15 mm) 20 ft. x 20 ft.
10680
3/4" (20 mm) 6,1 m x 6,1 m
1
Temperature rating of Viking Horizon
2
Based on NFPA-13. Other limits may apply depending on fire loading, sprinkler location, and other
requirements of the Authority Having Jurisdiction. Refer to specific installation standards.
3
Base part number shown. For complete part number, refer to Viking price list.
4
This chart shows listings and approvals available at time of printing. Other approvals are in process.
Check with the manufacturer for additional approvals.
5
For areas of coverage smaller than shown, use the "Minimum Water Supply Requirement" for the next
larger "Area of Coverage" listed for the sprinkler used. The distance from sprinklers to walls shall not
exceed one-half the sprinkler spacing indicated for the "Minimum Water Supply Requirement" used.
6
Metric K-factor shown is for use when pressure is measured in kPa. When pressure is measured in
BAR, multiply the metric K-factor shown by 10.0.
7
Listing is limited to Light Hazard Occupancies with smooth, flat, horizontal ceilings.
8
Accepted for use by City of New York Department of Buildings, MEA 89-92-Vol. IX.
1/2" NPT Sprinklers:
P/N 08498 (std. orifice)
P/N 10485 (large orifice)
Mirage
®
®
Nominal
Highest Ambient
Temperature
Temperature Allowed
1
Rating
at Ceiling
165 °F (74 °C)
100 °F (38 °C)
Areas of Coverage
Model B-1 Standard Orifice Horizon
Extended Coverage Concealed Sprinkler
Max. Area
Nominal
5
K-factor
6
L x W
16 ft. x 16 ft.
5.5
Listed for this spacing as Quick Resp. Ext. Coverage Sprin-
7,9
kler. See Quick Resp. Ext. Coverage Sprinkler page 58 a-d.
18 ft. x 18 ft.
5.5
Listed for this spacing as Quick Resp. Ext. Coverage Sprin-
kler. See Quick Resp. Ext. Coverage Sprinkler page 58 a-d.
7,9
20 ft. x 20 ft.
5.5
40 gpm @ 53.0 psi
7,9
151,4 L/min @ 368 kPa
Areas of Coverage
Model B-2 Large Orifice Horizon
Extended Coverage Concealed Sprinklers
Max. Area
Nominal
5
of Coverage
6
K-factor
L x W
8.0
11,5
8.0
11,5
8.0
11,5
Footnotes
®
Mirage
®
Concealed Sprinkler is stamped on the sprinkler body.
Sprinkler 87 a
®
HORIZON
MIRAGE
EXTENDED COVERAGE
20 ft x 20 ft (6,1 m x 6,1 m)
CONCEALED SPRINKLERS
3/4" NPT Sprinkler:
P/N 10680
(large orifice)
Cover Plate Assembly: P/N 09804
Figure B
Required
Cover Assembly
2
Temperature Rating
165 °F (74 °C)
®
®
Mirage
Minimum
Approvals
Water Supply
7
UL
C-UL
Requirements
Yes
Yes
®
®
Mirage
Minimum
Approvals
Water Supply
7
UL
Requirements
Listed for this spacing as Quick Response
Extended Coverage Sprinklers. See Quick Re-
sponse Extended Coverage Sprinkler page 58 a-d.
Listed for this spacing as Quick Response
Extended Coverage Sprinklers. See Quick Re-
sponse Extended Coverage Sprinkler page 58 a-d.
40 gpm @ 25.0 psi
Yes
151,4 L/min @ 174 kPa
Replaces page 87 a-d, dated August 4, 1998
(added new Model B-2 Part Number 10680).
®
4
7
8
NYC
Yes
4
7
C-UL
--
Yes
--

Advertisement

loading

Summary of Contents for Viking HORIZON MIRAGE B-1

  • Page 1 Authority Having Jurisdiction. Refer to specific installation standards. Inside the body of the sprinkler, the de- Base part number shown. For complete part number, refer to Viking price list. flector and sealing assembly are held in This chart shows listings and approvals available at time of printing. Other approvals are in process.
  • Page 2 Automatic-Fire”) or contact Viking. C36000 less of the standard used, the instal- Fusible Link Assembly*: Nickel Alloy Viking Technical Data may be found on lation must be acceptable to all and Eutectic Solder The Viking Corporation’s Web site at Authorities Having Jurisdiction.
  • Page 3 3. Use only the special wrenches bly. ments when subject to corrosive at- designed for installing Viking Ho- 2. Remove the plastic protective mospheres. ® ® rizon...
  • Page 4 Sprinkler 87 d February 11, 1999 ® ® HORIZON MIRAGE EXTENDED COVERAGE TECHNICAL DATA 20 ft x 20 ft (6,1 m x 6,1 m) CONCEALED SPRINKLERS ® ® nance instructions and follow all king Horizon Mirag e Extended 4. Remove the sprinkler from the pip- ing in which it is installed: Using Coverage Concealed Sprinklers, re- warnings and instructions.