Table 4
Series
Amperage
DS361UX
30A
DS362UX
60A
DS363UX
100A
DS361FX
30A
DS362FX
60A
DS363FX
100A
b. Maximum wire sizes are recommended based on NEC minimum
wire bending space at each terminal per designated enclosure. Select
wire gauge per NEC standard.
c. Table 4 lists maximum wire gauges for 55°C ambient temperature.
d. Use copper wire only. Wire to be rated at 75/90°C.
6.
For fusible disconnects, install Class J fuses. Contact Eaton's
Bussmann Division for more fuse information.
7 .
Test wiring for good connection by performing a continuity check.
Also, check for unwanted grounds with an insulation resistance tester.
WIRING DIAGRAM
CAUTION
To avoid the risk of explosion, clean both machined joint surfaces
of body and cover before closing. Dirt or foreign material must not
accumulate on flat machined joint surfaces. Surfaces must seat fully
against each other to provide a proper explosionproof joint.
8.
Make sure that operator and fork are in the OFF position.
9.
Fully tighten all cover bolts. See Table 5.
Table 5
Series
Cover Screw
DS361UX
5/16"-18
DS362UX
3/8"-16
DS363UX
3/8"-16
DS361FX
3/8"-16
DS362FX
3/8"-16
DS363FX
1/2"-13
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with
Eaton's Crouse-Hinds Division's "Terms and Conditions of Sale," and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use and assumes
all risk and liability whatsoever in connection therewith.
Terminal Torque Value
Wire Range
in.-lb.
#10-#8 AWG
35-40
#6-#3 AWG
45
#1-1/0 AWG
50
#10-#8 AWG
35-40
#6-#3 AWG
45
#1-1/0 AWG
50
Figure 3
Torque Value
ft.-lb.
N-m
20-25
27-34
35-40
48-54
35-40
48-54
35-40
48-54
35-40
48-54
40-45
54-61
Eaton's Crouse-Hinds Division
1201 Wolf Street Syracuse, New York 13208 • U.S.A.
Copyright© 2015
N-m
To avoid the risk of explosion, all unused conduit openings must be
closed properly with an approved plug, drain or breather such as the
4-5
Crouse-Hinds series PLG Plugs or ECD Breather/Drains. NO CONDUIT
5
OPENINGS ARE TO BE ADDED IN THE FIELD.
6
4-5
MAINTENANCE
5
6
To avoid electrical shock and personal injury, always disconnect
primary power source before opening enclosure for inspection or service,
and lock them out.
1.
Electrical and mechanical inspections must be done on a regular basis.
It is recommended that inspections be performed a minimum of once a
year.
2.
If necessary to open enclosure for inspection or service, always
disconnect primary power source and refer to cautionary statement or
nameplate before opening cover. Area must be free of flammable gases
and vapor before opening cover.
3.
Perform visual check for undue heating evidenced by discoloration of
wires or other components, damage or worn parts or leakage evidenced
by water or corrosion in the interior.
4.
Electrically check to make sure that all connections are clean and tight and
that contacts in the components make and break as required.
5.
Mechanically check that all parts are properly assembled and operating
mechanisms move freely.
a. For more operator adjustment instructions, see Figure 4.
Fork Adjustment
1.
Assemble operator into cover.
2.
Measure distance from body flange to bottom toggle (Dimension A).
3.
Measure distance from inside of cover to bottom of fork (Dimension B).
4.
Adjust fork up or down so that (B - A - 0.12").
5.
Move breaker toggle to "off" position and operator handle to "off"
position.
6.
Close cover and check breaker operation.
7 .
Adjust fork up or down to optimize breaker operation.
Stop Adjustment
1.
Move operator to "on position. "
2.
Put light pressure on handle in the "on" direction and hold in that position.
Fork should be touching toggle.
3.
Turn stop screw until it touches handle.
4.
Tighten stop nut.
5.
Move operator to "off" position.
6.
Put normal pressure on handle in the "off" direction until the handle stops.
Hold in that position. This represents the reset position.
7 .
Turn stop screw until it touches handle.
8.
Tighten stop nut.
Eaton recommends an Electrical Preventive Maintenance Program as described
in the National Fire Protection Association Bulletin NFPA 70B.
CAUTION
WARNING
Figure 4
Supercedes 07/15
IF 1772
Revision 2
Revised 11/15