Thank you for buying this product, our company is sure that you will be
more than satisfied with the performance of the product.
This product is supplied with a "WARNINGS" leaflet and an
"INSTRUCTION MANUAL". These should both be read carefully as
they provide important information about safety, installation,
operation and maintenance.
This product complies with recognized technical standards and safety
regulations. We declare that this product is in conformity with the
following European Directives: 89/336/EEC and 73/23/EEC (amended
by RL 91/263/EEC, 92/31/EEC and 93/68/EEC).

1) GENERAL OUTLINE

The POLLUCE 2M Mod. Unit is suitable for operating 1 or 2 ARM2
series controllers, and has been designed to automate various types of
overhead doors.
The unit can be: Included with the ARM2 series (fig. 1).
Fitted onto a wall panel (fig. 2) for use with the series without the control
unit (ARM2-SQ series). 2 possible configurations are available in case
two-motor overhead door automation is required:
No. 1 ARM2 + No. 1 ARM2-SQ.
No. 2 ARM2-SQ + No. 1 2M POLLUCE with panel, wall-mounted.

2) TECHNICAL SPECIFICATIONS

Power supply voltage:
No load current:
Max. absorbed rating:
Power supply to accessories:
Max. current for accessories:
Working temperature:
Max. No. of manoeuvres in 24h:
Automatic closing time TCA:
Operation time TW:
Time-set courtesy light:
Blinker:
(*) For 110V power supply see fuse values in figs. 1 - 2.

3) FUNCTION LOGIC

START: four-step logic: (DIP5 OFF)
gate closed:
on opening:
gate opened:
on closing:
after stopping:
START: two-step logic: (DIP5 ON)
door closed:
on opening:
door opened:
on closing:
after stopping:
STOP: Stops the gate until restart
PHOT: Photocell input
Configured by means of DIP3
SWO: Stops door at end of opening stroke
SWC: stops door at end of closing stroke
SCA: Door open warning light
with door closed:
with door opening:
with door opened:
with door closing:

4) DIP-SWITCH SELECTION

DIP1: Swift Closure (SCL)
ON: When there is movement across the photocells, either on entry
or on exit, at the last disengagement of the photocells, the door closes
automatically without waiting for the TCA to end. This function is
recommended whenever the safety conditions of the installation allow
the configuration of DIP3-ON (the photocells are only active on closing).
OFF: Function deactivated.
DIP2:Blocks impulses on opening (IBL)
ON: Will not accept START commands during opening phase.
OFF: Accepts START commands during opening phase.
DIP3:Photocell on opening (FCH)
230V±6% 50/60Hz (*)
150 (varies depending
on accessories)
300W for motor
24Vac ± 20%
0.25A (6VA)
-20° +60°C
40
adjustable 0 - 90 sec
adjustable 0 - 40 sec
230V - 40W max. 90 sec
230V - 40W max.
opens
stops and inserts TCA if configured
closes
stops but will not insert TCA
moves to open
opens
stops and inserts TCA if configured
closes
opens
opens
off
on
on
blinking
GB
ON: Photocell is only active on closing.
OFF: Photocell is active both on closing and opening.
DIP4:Automatic closing time (TCA)
ON: Automatic closing time inserted (adjustable 0 - 90 sec with trimmer TW).
OFF: Automatic closing time excluded.
DIP5:Control logic (2P/4P)
ON: Activates two-step logic (see paragraph on start).
OFF: Activates four-step logic (see paragraph on start).
DIP6:Not used (always leave OFF).
5) TRIMMER ADJUSTMENT
TCA Sets the automatic closing time, after which the door
closes automatically (adjustable from 0 to 90 sec).
TW
Sets the motor operating time, after which the motor stops
(adjustable from 0 to 40 sec). Allows the motor to be stopped in the
case where, for any reason, the limit microswitch is not detected.
6) MOTOR TORQUE SETTING
The POLLUCE 2M mod. board is supplied by a transformer which also
allows the electric motor torque to be selected.
DANGER: The transformer terminals are connected to the mains
power supply. Disconnect the mains power supply before doing
any work on the installation. To select the torque tap, remove the
transformer protection and remember to replace it afterwards.
The selection is carried out by moving connection "55" of the transformer
to one of the 4 taps "T1 - T2 - T3 - T4" as shown in figs. 1 -2.
In the case where the overhead door produces excessive friction,
which can be detected by the force required to open the door
manually, check the balancing or carry out the necessary maintenance
to eliminate it.
WARNING: Excessive torque adjustment may jeopardize the anti-
squash safety function.
On the other hand insufficient torque adjustment may not guarantee
correct opening or closing strokes.
7) POLLUCE 2M TERMINAL BOARD CONNECTIONS (fig. 3)
JP14
1-10
Single phase power supply 230V±6% 50/60Hz (1=L/10=N)
2-5
Not used
3-4
M1 motor capacitor
11-12-13
M1 Motor connection (12 common, 11-13 run)
6-7
M2 motor capacitor
14-15-16
M2 motor connection (15 common, 14-16 run)
8-17
Time-set courtesy light connection (25W max.)
9-18
Blinker connection 230V (40W max.)
JP7
25
Control common terminal (corresponding to terminal 19)
19-20
Start button (opens - closes N.O.)
19-26
Lock button (N.C.). When not used leave bridged.
19-21
Electric edge or photocell input (N.C.).
When not used leave bridged.
19-22
Closing limit microswitch connection (SWC)
19-27
Opening limit microswitch connection (SWO)
28-23
24 Vac 0.25A max. (6VA) outlet (power supply to
photocell or other devices)
23-29
Gate open warning light 24V (3W max.)
24-30
Antenna input for radio receiver board (24 signal - 30 braid).
JP1
Radio receiver board connector. 1-2 channels.
JP8
Second radio channel output from the double-channel
receiving board (not fitted) (dry contact N.O.)
8) POLLUCE 2E TERMINAL BOARD CONNECTIONS (fig. 4)
Another version is also available which allows the connection of a 12V
electric lock. This version is known as POLLUCE 2E.
Fig. 4 only shows the part of the terminal board regarding the electric
lock connection. For all other connections, reference should made to
the terminal board in fig. 3.
D811199A Ver. 02 - 3