4.- Setup and measurements
To enter the SETUP mode, press the setup key (9), for more than 1s. If all the capacitors are disconnected, the access in immediate, otherwise a disconnection sequence
starts and then accesses to setup menu. In the SETUP mode, if no key is pressed for 3 minutes, the equipment exits such mode and returns to normal operation mode.
Key to access the SETUP mode:
- Long push to enter and exit SETUP mode. Also DELETE max values when
in the measuring mode
- Short push: to change from display mode to edit mode and vice versa.
If no key is pushed during more than 3 minutes, the regulator exits the SETUP
mode without changing the setup.
:
Symbol showing which parameter is being displayed or edited.
- In the display mode: Cursors to select an option.
- In edit mode: Change a parameter value
Display SETUP Parameters
6.-
C/K table depending on initial cos , desired cos and CT ratio
CT Ratio
CT
2.5
5,00
7.5
10,0
150/5
0,12
0,24
0,36
0,48
200/5
0,09
0,18
0,27
0,36
250/5
0,07
0,14
0,22
0,29
300/5
0,06
0,12
0,18
0,24
400/5
0,05
0,09
0,14
0,18
500/5
0,07
0,11
0,14
600/5
0,06
0,09
0,12
800/5
0,07
0,09
1000/5
0,05
0,07
1500/5
0,05
2000/5
2500/5
3000/5
4000/5
For different voltages (V) of 400V, table result must be multiply for 400/V, or calculate C/K parameter using the expressions.
7.- Technical Service
For any inquiry about the regulator operation or in case of malfunction, see
detailed manual at www.circutor.es or contact with technical service.
points to the option
Edit SETUP parameters
Description
MENU OPTIONS
Target cos  (def=1)
Reactive I of 1
C/K adjustment
Range: 0.02 – 1.00
See paragraph 6
Program setting
Depends on the kvar
relationship between
successive steps.
See paragraph 4.2
Delay for successive
steps (2 -99 cycles) .
Selection of Nr of
outputs , max 6 or 12
depending on type
CT connection . See
paragraph 4.3. The
display shows T1, T2,
T3, T4, T5 or T6.
Accept the option
giving cos between
0.7 Ind and 0.98 Cap
CT primary current
setting. See
paragraph 4.4
Lower step reactive power (kvar) at 400V
12,5
15,0
20,0
25,0
30,0
37,5
0,60
0,72
0,96
0,45
0,54
0,72
0,90
0,36
0,43
0,58
0,72
0,87
0,30
0,36
0,48
0,60
0,72
0,90
0,23
0,24
0,36
0,48
0,58
0,67
0,18
0,22
0,29
0,36
0,45
0,54
0,15
0,18
0,24
0,30
0,36
0,45
0,11
0,14
0,18
0,23
0,27
0,33
0,09
0,11
0,14
0,18
0,22
0,27
0,06
0,07
0,10
0,12
0,14
0,18
0,05
0,07
0,09
0,11
0,13
0,06
0,07
0,09
0,10
0,05
0,06
0,07
0,09
0,05
0,06
4.1.- RUN & Measuring mode
In normal operation mode (RUN mode) the regulator display may show different
parameters (V, I, cos, etc.) The displayed parameter is pointed by the sign
By default the regulator displays the cos, but pushing the keys
following parameters can be explored: Current (I), Current harmonics (THD), Mains
Voltage (V), Maximum current (I MAX) y Maximum voltage (V MAX). If both keys
are pushed simultaneously the regulator displays the Nr of connected steps.
A long push of
key in maximum values screen causes de deletion of recorded
max values, in other parameters visualization screens we will go to SETUP
screens.
4.2.- Program selection
This setting depends on the kvar ratio between the different capacitor steps. For
instance if the bank is 10+20+20+20 kvar the program is 1:2:2:2, so the option 122
must be selected. The program P00 of simulation allows to see on screen the steps
that it would connect without managing to do it.
Display
Program
P00
Simulation
step,
st
4.3.- Selecting the CT connection phase
Choose among the options in the table depending on CT connection and the
phases where V is measured. In normal installations (no exported energy) choose
the option for which the displayed cos is between 0.7 Ind and 0.98 Cap.
V-I phase shift at
Display
cos=1
T1
T2
T3
T4
T5
T6
4.4.- Selecting the rated primary current of CT
If the LED is blinking indicates that we are in SETUP mode and
adjusting primary CT current. When in RUN mode or when Iprimary is displayed,
the LED indicates whether the displayed current has a scale factor x1 (LED OFF)
or x10 (LED ON)
5.- Error Codes
ERR CODE
DISPLAY
000
Alll zeros
cos  and E.02
E.02
al t ernate blinking
cos  and E.03
E.03
al t ernate blinking
cos  and E.04
E.04
al t ernate blinking
cos  and E.05
E.05
al t ernate blinking
C/K calculation:
40,0
50,0
60,0
75,0
80,0
If It is the primary rated current of the CT and
Ic the rated current of the lower capacitor step,
the C/K must be set according to the
calculations shown below:
0,96
0,72
0,87
Example : CT current ratio = 500/5
0,54
0,72
0,87
Lower step power: 60 kvar at 400V
0,48
0,60
0,72
0,90
0,96
0,36
0,45
0,54
0,68
0,72
K
0,29
0,36
0,43
0,54
0,57
0,19
0,24
0,29
0,36
0,38
C
0,14
0,18
0,22
0,27
0,28
0,12
0,14
0,17
0,22
0,23
0,10
0,12
0,14
0,18
0,19
0,07
0,09
0,11
0,14
0,14
CIRCUTOR S.A.
Vial Sant Jordi, s/n
08232 - Viladecavalls (Barcelona) SPAIN
TEL – (+34) 93 745 29 00 & fax – (+34) 93 745 29 14
E-mail : sat@circutor.es
computer max 6f / max 12f
Display
Program
Display
111
1:1:1:1
T11
122
1:2:2:2
T22
124
1:2:4:4
T24
248
1:2:4:8
T48
112
1:1:2:2
T12
Measuring phases
for V
30º
L3-L2
270º
L3-L2
150º
L3-L2
210º
L3-L2
90º
L3-L2
330º
L3-L2
DESCRIPCIÓN
Load current below measuring threshold or
CT not connected
Overcompensation. The regulador is asking to
disconnect Cs and they are all disconnected
Sub-compensation. The regulator is asking for more
Cs and they are all connected
Over current. The current is + 20%. Above primary
rated current
Overvoltage. Vol t age is +15%. Above rated vol t age
500
60
.
000
100
;
I
C
5
, 1
73
400
Ic
86
7 ,
/
K
, 0
867
K
100
.
the
Program
1:1:1:1 (Total)
1:2:2:2 (Total)
1:2:4:4 (Total)
1:2:4:8 (Total)
1:1:2:2 (Total)
Phase where TC is
connected
L3
L1
L2
L3 (CT reversed)
L1 (CT reversed)
L2 (CT reversed)
ACTUACIÓN
Forces all the
outputs OFF
NO ACTION
NO ACTION
NO ACTION
NO ACTION
It
K
5
Q
I
C
3
V .
86
7 ,
A
Ic
C K
/
K
M98231001-03-16A.doc