1MRS756879 D
2.5.1
2.5.1.1
Table 74:
CTRL.LLN0 Local remote station off
IEC 61850 name
SA name
CTRL.LLN0
.LocRem.stVal
2.5.1.2
Table 75:
LD0.LPHD1 System values
IEC 61850 name
SA name
LD0.LPHD1
.NumCmpChg.stVal
.NumPwrUp.stVal
.PhyHealth1.stVal
.PhyHealth2.stVal
.WacTrg.stVal
.WrmStr.stVal
2.5.1.3
Table 76:
LD0.DNPGGIO1 Active parameter setting group
IEC 61850 name
SA name
LD0.DNPGGIO1
.ActSG.stVal
2.5.1.4
Table 77:
LD0.LEDGGIO1 LHMI LED indications (3 states)
IEC 61850 name
SA name
LD0.LEDGGIO1
.ISCSO1.stVal
.ISCSO2.stVal
.ISCSO3.stVal
.ISCSO4.stVal
Table continues on next page
RED615
Point List Manual
System functions
CTRL.LLN0 Local remote station off
Description
Off=0; Loc=1; Rem=2;
-
Station=3
LD0.LPHD1 System values
Description
-
Num.of comp. changes
-
Num.of power ups
Warning
Warning code
Internal Fault
Internal fault code
-
Num.of watchdog resets
-
Num.of warm starts
LD0.DNPGGIO1 Active parameter setting group
Description
-
Active setting group
LD0.LEDGGIO1 LHMI LED indications (3 states)
Description
-
LED 1 state
-
LED 2 state
-
LED 3 state
-
LED 4 state
DNP3 data mappings
Values
S
Arg 1,2,3,4
0...3
R
0,3,0,3
Values
S
Arg 1,2,3,4
0...65535
R
0,65535,0,65535
0...65535
R
0,65535,0,65535
0...65535
R
0,65535,0,65535
0...65535
R
0,65535,0,65535
0...65535
R
0,65535,0,65535
0...65535
R
0,65535,0,65535
Values
S
Arg 1,2,3,4
1...6
R
1,6,1,6
Values
S
Arg 1,2,3,4
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
Section 2