Troubleshooting - Carel humiSonic User Manual

Ultrasonic humidifiers
Hide thumbs Also See for humiSonic:
Table of Contents

Advertisement

Available languages

Available languages

ENG

11.1 Troubleshooting

NOTICE:
if the problem identified cannot be solved using the following
guide, contact CAREL technical service.
1. Firstly, check the humidifier and the surrounding area.
Problem
Cause
No atomised water
Power supply
production
Feedwater system
The quantity of atomised
Power supply
water is too low
Feedwater system
Other
No atomised water
Dust and foreign matter accumulated in the tank (*)
Transducer deterioration
production
The quantity of atomised
Dust and foreign matter accumulated in the tank (*)
Scale build-up on the surface of the piezoelectric transducers (*)
water is too low
(*) These malfunctions can be avoided by carrying out preventive
maintenance.
2. If the cause has not been identified with the previous checks, there
may be faulty components. Check the inside of the humidifier.
Problem
Cause
No atomised water
Feedwater system
production
Other
The quantity of atomised
Water level overflow
water is too low
Direct version for room applic. +0300062EE - rel. 1.4 - 24.09.2020
Humidifier switch in the OFF position
No power
Power supply fault
Valve closed upstream
Low power supply voltage
Water level during production is too
high and overflowing
The humidifier is not installed
horizontally
Verification
Float level sensor fault
Empty the tank, remove the
electronic board and check
Float level sensor blocked
continuity of the level sensor
Fill valve fault
No water filled even when the tank
has been emptied
The fan cables are loose or
Check connection after removing
detached
the humidifier cover
Float level sensor blocked
If the water level in the tank
reaches the overflow pipe, remove
the connector from the control
board and check continuity of the
level sensor
Fill valve fault
Water is filled even after switching
off the appliance
26
Verification
Check the switch
Measure the voltage at the
humidifier input terminals
Measure the voltage at the power
supply output terminals
Check
Check the voltage at the power
supply output terminals
Check visually
Check visually
The average life of the transducer is
around 10,000 to 15,000 operating
hours
Visually check the inside of the tank Clean the inside of the tank
Solution
Contact service to replace the level
sensor
Clean the sensor. If normal
operation is not restored, replace
Replace the valve
Clean the sensor. If normal
operation is not restored, replace
Restore correct connection to the
terminals
If there is continuity, contact service
to replace the level sensor
Replace the fill valve
Solution
Switch ON
Connect power
Replace the power supply
Open the valve
Replace the power supply, if
damaged
See the following table
Adjust
Clean the inside of the tank
Replace
and replace the transducers
Tab. 11.b
Tab. 11.c