Introduction

This installation guide provides instructions for
installation, startup, and adjustment. To receive a copy
of the instruction manual, contact your local Fisher
Sales Office or Sales Representative or view a copy
at www.emersonprocess.com/regulators. For further
information refer to:
Type SR5 instruction manual (form 5786,
D103099X012).

P.E.D. Categories

This product may be used as a pressure accessory with
pressure equipment in the following Pressure Equipment
Directive 97/23/ EC categories. It may also be used
outside of the Pressure Equipment Directive using sound
engineering practice (SEP) per table below.
ProDuCt SIzE
DN 15, 20, and 25 (1/2 thru 1-inch)
DN 40 x 25, 40, and 50
(1-1/2 x 1, 1-1/2, and 2-inch)
DN 80 (3-inch)

Specifications

available Constructions
type Sr5: Pressure reducing regulator designed for
use in sanitary applications. DN 15, 20, 25, 40 x 25,
50, and 80 (1/2, 3/4, 1, 1-1/2 x 1, 2, and 3-inch) body
sizes are suitable for controlling steam, liquids and
gasses. DN 40 (1-1/2-inch) is suitable for steam and
gasses, it is not for use on liquids. End connections
match up to Tri-Clamp® sanitary fittings.
Maximum Inlet and outlet Pressures
DN 15 to 40 (1/2 to 1-1/2-inch):
14,5 bar at 65 °C (210 psig at 150 °F)
12,4 bar at 135 °C (180 psig at 275 °F)
11 bar at 204 °C (160 psig at 400 °F)
DN 50 and 80 (2 and 3-inch):
Maximum Inlet Pressure:
14,5 bar at 65 °C (210 psig at 150 °F)
12,4 bar at 135 °C (180 psig at 275 °F)
11 bar at 204 °C (160 psig at 400 °F)
1. The pressure/temperature limits in this installation guide and any applicable standard or code limitation should not be exceeded.
CatEgorIES FluID tyPE
SEP
I
1
II
(1)
www.emersonprocess.com/regulators
Maximum Outlet Pressure:
10,3 bar at 65 °C (150 psig at 150 °F)
8,62 bar at 135 °C (125 psig at 275 °F)
7,58 bar at 204 °C (110 psig at 400 °F)
Proof test Pressure
All Pressure Retaining Components have been
proof tested per Directive 97/23/EC - Annex 1,
Section 7.4
outlet Pressure ranges
DN 15, 20, 25 and 40 x 25 (1/2, 3/4, 1 and
1-1/2 x 1-inch): 0,2 to 0,5 bar (2 to 8 psig), 0,4
to 1,7 bar (5 to 25 psig), 0,7 to 3,4 bar (10 to
50 psig), 1,7 to 6,2 bar (25 to 90 psig), and 2,4
to 9,3 bar (35 to 135 psig)
DN 40 (1-1/2-inch): 0,4 to 1,7 bar (5 to 25 psig), 0,7
to 3,4 bar (10 to 50 psig), 1,7 to 5,2 bar (25 to 75
psig), and 2,4 to 6,9 bar (35 to 100 psig)
DN 50 and 80 (2 and 3-inch): 0,7 to 1,7 bar (10 to
25 psig), 1,0 to 3,4 bar (15 to 50 psig) and 1,7 to
5,2 bar (25 to 75 psig)
temperature Capabilities
Metal Seat (316l SSt)
Ethylenepropylene (EPDM) Diaphragm and O-ring:
-28 to 135 °C (-20 to 275 °F)
316L SST Diaphragm and PTFE/FKM O-ring:
-6 to 204 °C (20 to 400 °F)
PTFE/FKM Diaphragm and O-ring:
-6 to 204 °C (20 to 400 °F)
Soft Seat (PtFE/316l SSt)
Ethylenepropylene (EPDM) Diaphragm and O-ring:
-28 to 65 °C (-20 to 150 °F)
316L SST Diaphragm and PTFE/FKM O-ring:
-6 to 65 °C (20 to 150 °F)
PTFE/FKM Diaphragm and O-ring:
-6 to 65 °C (20 to 150 °F)
PEEK Seat (PEEK/316l SSt)
Ethylenepropylene (EPDM) Diaphragm and O-ring:
-28 to 135 °C (-20 to 275 °F)
316L SST Diaphragm and PTFE/FKM O-ring:
-6 to 204 °C (20 to 400 °F)
PTFE/FKM Diaphragm and O-ring:
-6 to 204 °C (20 to 400 °F)
Type SR5
(1)
(1)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Fisher SR5 and is the answer not in the manual?

Questions and answers

Summary of Contents for Emerson Fisher SR5

  • Page 1 Installation Guide Type SR5 English – February 2006 Introduction This installation guide provides instructions for Maximum Outlet Pressure: 10,3 bar at 65 °C (150 psig at 150 °F) installation, startup, and adjustment. To receive a copy 8,62 bar at 135 °C (125 psig at 275 °F) of the instruction manual, contact your local Fisher 7,58 bar at 204 °C (110 psig at 400 °F) Sales Office or Sales Representative or view a copy...
  • Page 2 Type SR5 Installation Regulator operation below the maximum pressure limitations does not preclude the possibility of damage from external sources or debris in the line. The regulator should be inspected for damage after any overpressure condition. Only qualified personnel should install or service a regulator.
  • Page 3 Type SR5 t-haNDlE oPtIoN vaCuuM ProtECtIoN oPtIoN StaNDarD rEgulator wIth ElaStoMErIC DIaPhragM SoFt SEat oPtIoN vIEw b — MEtal DIaPhragM For StaNDarD rEgulator Figure 1. Type SR5 Sanitary Regulator Assembly Parts list Description Description Bolted Clamp Body Hex Nut Plug (metal seat) Hex Nut Plug O-Ring Adjusting Screw...
  • Page 4 For further information visit www.emersonprocess.com/regulators The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls, Inc., a business of Emerson Process Management.

Table of Contents