Button Press - Siemens Desigo PXG3.L Manual

Bacnet router
Hide thumbs Also See for Desigo PXG3.L:

Advertisement

LEDs
HMI/Tool
RUN
FLT
8 7 6 5 4 3 2 1
Service button
1
4 / 10
Siemens
Building Technologies
LED
Color
Activity
· Continuously ON
RUN
Green
· Continuously OFF
· Flashing
· Continuously OFF
FLT
Red
· Continuously ON
· Flashing
INF
--
--
COM1
· Flashing
Yellow
COM2
· Flashing
Yellow
· Continuously OFF
SVC
Red
· Continuously ON
· Flashing
· Flashing per wink
command *)
· Continuously ON
Ethernet
Green
· Continuously OFF
1 / 2
· Flashing
· Continuously ON
Yellow
· Continuously OFF
Wink command
*)
pattern:

Button Press

Description
· Short
1
Physical identification on the network (Ethernet).
To reset the device into the factory state please follow these steps:
1. Power off device.
2. Power on the device.
3. Wait for all LEDs to light up and turn off again,
then push down SVC button.
4. Keep SVC button pressed until the green RUN LED flashes,
then release button.
5. Wait for device to fully start up unconfigured
(RUN LED on, SVC LED flashes).
The device has now lost any password and other settings.
Only the IP network settings remain the same as before.
PXG3...
BACnet router for Ethernet - LONWORKS - MS/TP
Function
· Device ready.
· At least one internal power supply out
of range.
· Start-up of device.
· OK
· HW fault or program fault.
· Incorrect or corrupt FW.
(Not used)
· Sends MS/TP packages.
· Sends L
W
ON
ORKS
(PXG3.L only).
· Configured.
· Defective Hardware.
· Unconfigured.
· Physical identification of the router.
· Link active
· Link inactive
· Network activity
· Link 100 Mbps
· Link 10 Mbps
21s
5 Hz
1s
2s
2s
packages
9222z02
5 Hz
1s
CM1N9270en_06