Be sure to use the rated voltage and air conditioners dedicated
circuit for the power supply, and the power cord diameter must
meet the national requirements.
When the maximum current of air conditioner is 16A, it must use
the air switch or leakage protection switch equipped with
protection devices.
The normal operating range is 90%-110% of the local rated voltage.
The minimum clearance between the air conditioner and the
combustibles is 1.5 m.
The
interconnection cord
units. You must first choose the right cable size before preparing it
for connection.
Cable Types:
Outdoor Power Cable: H07RN-F or H05RN-F;
Interconnection cord
Minimum Cross-Sectional Area of Power Cable and
Interconnection cord
North America
Appliance
Amps(A)
10
13
18
25
30
40
The size of the
switch needed is determined by the maximum current of the unit.
The maximum current is indicated on the nameplate located on
the side panel of the unit. Refer to this nameplate to choose the
right cable, fuse, or switch.
Note: Core number of cable refer to the detailed wiring diagram
adhered on the unit which you purchased.
Electrical Safety Requirements
enables connect the indoor and outdoor
: H07RN-F or H05RN-F;
Rated Current
AWG
of Appliance(A)
18
3 and
16
6 and
14
10 and
12
16 and
10
25 and
8
32 and
interconnection cord
- 13 -
Notices for installation
Other Regions
Nominal Cross-
Sectional Area(mm )
6
10
16
25
32
40
, power cable, fuse, and
2
.
0 75
1
1 5 .
2 5 .
4
6