SFU-0302 SSE
Error Description
In case of connecting the
converter with a PC or
after launching the SW
SFU-Terminal the
Converter is not
detected and not
recognized
Start with push buttons
not possible
Spindle does not start,
in spite of a valid signal
for Start
BMR GmbH
M a n u a l
Cause
Incorrect connection cable or wiring
fault
In case of using RS232
In case of using a USB-RS232
converter the USB-driver is not
installed correctly.
unsure
Start button deactivated
An input is assigned with the function
Emergency Stop and configured as
"Low Active".
> This is default state on delivery
The evaluation of the temperature
sensor is activated in the spindle
characteristic, but it is not connected
or a sensor isn't implemented within
the spindle
-> in this case Error is indicated,
additionally
The spindle test is engaged
2014-03-17
Fixing
> Check cable for proper Pinout.
> Verify at USB cables that it's length is not
longer than 2m
> Try to use original BMR cables, only.
> Use the USB-Interface at the PC together
with a USB-RS232 converter.
> For use with SFU 0303 a specific RS232
cable is required
install driver
Restart SFU-Terminal
Enable Start button by un-checking the
checkbox "Block Start Button"
> For unlocking, a signal of "HI" / +24V is
required at this input
> Deactivate this function or setup as "High
Active"
> Connect the temp sensor wires with the
SFU .
> un-check the button "Temp Sensor" in the
spindle characteristic in SFU-Terminal
> Check cable and connections for proper
wiring or short circuit
> Check spindle
– 24–