Parts Ordering - Emerson Fisher SS-83 Instruction Manual

Angle valve
Table of Contents

Advertisement

SS-83 Valve
March 2013
4. Remove any stem connector parts or locknuts. Loosen the packing flange nuts (key 8).
5. Remove the seat ring (key 2) and the valve plug and stem assembly (key 4) through the bottom of the valve body.
Set removed parts on a protective surface to prevent damage to gasket or seating surfaces.
6. Inspect the plug and stem assembly for nicks, scratches, scoring, or signs of galling. (If the stem is worn, packing
leakage can result.) Clean the gasketed surfaces and replace the seat ring gasket (key 3), seat ring (key 2), and valve
plug and stem assembly (key 4).
7. Tighten the packing flange nuts snuggly.
8. Before putting the valve in service, cycle the valve until packing friction is reduced to an acceptable level.
9. Install the actuator according to instructions in the appropriate actuator instruction manual. Install the valve back in
the line.
10. For spring-loaded PTFE V-ring packing, tighten the packing flange nuts until the shoulder on the packing follower
contacts the bonnet.
For graphite packing, tighten the packing flange nuts to the maximum recommended torque shown in table 1.
Then loosen the packing flange nuts, and retighten them to the recommended minimum torque shown in table 1. If
the stem diameter of your valve is not shown in the table, contact your Emerson Process Management sales office.
For ENVIRO-SEAL or HIGH-SEAL live-loaded packing, refer to the note at the beginning of the Maintenance section.
For other types of packing, contact your Emerson Process Management sales office.
11. Mount the actuator on the valve assembly and reconnect the actuator and valve stem according to the procedure
in the appropriate actuator instruction manual.

Parts Ordering

Each valve is assigned a serial number which can be found on the valve or on the nameplate. The nameplate will
normally be fitted to the actuator. Refer to this serial number when contacting your Emerson Process Management
sales office for technical assistance. When ordering replacement parts refer to this serial number and give the part
description from the following parts list.
WARNING
Use only genuine Fisher replacement parts. Components that are not supplied by Emerson Process Management should
not, under any circumstances, be used in any Fisher valve, because they may void your warranty, might adversely affect the
performance of the valve, and could cause personal injury and property damage.