Mitsubishi Electric MELSEC iQ-F Series Programming Manual page 91

Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

• In a selective transition, a convergence can be omitted by a jump transition or end transition.
(1)
(2)
(3)
(4)
(5)
The above program can be created by changing the steps other than the step of the leftmost branch to end
steps and changing the end step of the leftmost branch to a jump sequence.
For the operation method for changing steps, refer to the following.
GX Works3 Operating Manual
Simultaneous sequence (divergence/convergence)
All the steps branched from one step are activated simultaneously. When all the steps immediately before convergence are
activated and the common transition becomes TRUE, the active state transitions to the next step.
Item
Description
Divergence
(1)
(2)
(3)
(5)
(7)
Convergence
(1)
(3)
(4)
When transition (2) becomes TRUE during action of step (1), step (3) and step
(4) are sequentially executed. When the transition (5) becomes TRUE, a jump
sequence to step (1) occurs.
When the transition (2) becomes TRUE while the step (1) is active, both of the
step (3) and step (4) are activated at the same time.
The step (1) becomes inactive. However, if it is a coil HOLD step [SC], the step
holds the coil output or action according to its attribute.
Processing will proceed to step (7) when the transition (5) becomes TRUE and
to step (8) when the transition (6) becomes TRUE.
(4)
(6)
(8)
After the step (1) and step (2) immediately before the convergence become
active, the transition (3) is checked, then becomes TRUE, the step (4) is
activated.
The step (1) and step (2) become inactive. However, if it is a coil HOLD step
[SC], the step holds the coil output or action according to its attribute.
(2)
8 SFC PROGRAM
89
8.2 Structure
8

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-f fx5

Table of Contents