Retentive timer (low-speed timer/timer/high-speed timer), counter, and long counter
The following describes operations of the retentive timer (low-speed timer/timer/high-speed timer), counter, and long counter.
Ex.
A subroutine-type FB using a low-speed retentive timer
SM400
EN
■When "Yes" is selected for "Use MC/MCR to Control EN"
The current count value remain unchanged. ((1) in the following figure). The coil turns off ((2) in the following figure).
Sc
EN
ST0 (Count)
0
ST0 (Coil)
Sc: Scan
ST0 (Count): T0 (count value)
ST0 (Coil): T0 (coil)
EN is turned off. (User operation)
The coil turns off, but the current count value and the current state of the contact remain unchanged. (CPU module operation)
■When "No" is selected for "Use MC/MCR to Control EN"
The current count value and the current state of the coil remain unchanged. ((1) in the following figure).
Sc
EN
ST0 (Count)
0
ST0 (Coil)
Sc: Scan
ST0 (Count): T0 (count value)
ST0 (Coil): T0 (coil)
EN is turned off. (User operation)
The values remain unchanged. (CPU module operation)
APPX
116
Appendix 1 Operations of when the MC/MCR instructions are used to control EN
OUT
ST0
END
(1)
1
2
3
3
(2)
(1)
1
2
3
3
(1)
ENO
K3
3
3
3
3