C
G
ONFIGURATION
UIDELINES
The NFS-320 system ships assembled; description and some
options follow. See "Enclosures, Chassis, and Dress Plates" on
page 6 for information about mounting peripherals.
Stand-alone and network systems require a main display. On stand-
alone systems, the panel's keypad provides the required display. On
network systems (two or more networked fire panel nodes), at least
one NCD, NCA-2, NCS, or ONYXWorks annunciation device is
required. (For NCA-2, see DN-7047. For NCD, see DN-60974.)
M
S
C
AIN
YSTEM
OMPONENTS
NFS-320: The standard, factory-assembled NFS-320 system
includes the following components: one control panel mounted on
chassis (120 V operation — ships with grounding cable, battery
interconnect cables, and document kit); includes integral power sup-
ply mounted to the main circuit board; one primary display KDM-R2
keypad/display; and one cabinet for surface or semi-flush mounting.
Purchase batteries separately. One or two option boards may be
mounted inside the NFS-320 cabinet; additional option boards can
be used in remote cabinets. (Non-English versions also available.
NFS-320-SP, NFS-320-PO.)
NFS-320R: Same as NFS-320, but in red enclosure.
NFS-320C: Based on NFS-320 above. NFS-320C supports installa-
tion of an optional ACM-series annunciator in the same cabinet. UL-
and ULC-listed. (Non-English version also available: NFS-320C-
FR.) For NFS-320C, see DN-60085.
NFS-320CR: Same as NFS-320C but in a red enclosure. For NFS-
320C, see DN-60085.
NFS-320E: Same as NFS-320, but with 240 V operation. (Non-
English versions also available. NFS-320E-SP, NFS-320E-PO.)
TR-320: Trim ring for the NFS-320 cabinet.
N
O
ETWORKING
PTIONS
NCM-W, NCM-F: Standard Network Communications Modules. Wire
and multi-mode fiber versions available. See DN-6861.
HS-NCM-W(-2), HS-NCM-MF, HS-NCM-SF, HS-NCM-WMF(-2),
HS-NCM-WSF(-2), HS-NCM-MFSF: High-speed Network Commu-
nications Modules. Wire, single-mode fiber, multi-mode fiber, and
media conversion models are available. See DN-60454.
RPT-W, RPT-F, RPT-WF: Standard-network repeater board with wire
connection (RPT-W), multi-mode fiber connection (RPT-F), or allow-
ing a change in media type between wire and fiber (RPT-WF). Not
used with high-speed networks. See DN-6971.
ONYXWorks: UL-listed graphics PC workstation, software, and
computer hardware. See DN-7048 for specific part numbers.
NFN-GW-EM-3: NFN Gateway, embedded. See DN-60499.
NWS-3: NOTI•FIRE•NET™ Web Server. See DN-6928.
CAP-GW: Common Alerting Protocol Gateway. See DN-60756.
VESDA-HLI-GW: VESDAnet high-level interface gateway. See DN-
60753.
Page 4 of 7 — DN-7112:P • 12/20/2020
LEDSIGN-GW: UL-listed sign gateway. Interfaces with classic and
high-speed NOTI•FIRE•NET networks through the NFN Gateway.
See DN-60679.
OAX2-24V: UL-listed LED sign, used with LEDSIGN-GW. See DN-
60679.
A
P
S
UXILIARY
OWER
UPPLIES AND
ACPS-610: 6.0 A or 10.0 A addressable charging power supply. See
DN-60244.
APS2-6R: Auxiliary Power Supply. Provides up to 6.0 amperes of
power for peripheral devices. Includes battery input and transfer
relay, and overcurrent protection. Mounts on two of four positions on
a CHS-4L or CHS-4 chassis. See DN-5952.
FCPS-24S6/S8: Remote 6 A and 8 A power supplies with battery
charger. See DN-6927.
BAT Series: Batteries. NFS-320 uses two 12 volt, 18 to 200 AH bat-
teries. See DN-6933.
A
O
UDIO
PTIONS
NFC-50/100: 25 watt, 25 VRMS, emergency Voice Evacuation Con-
trol Panel (VECP) with integral commercial microphone, digital mes-
sage generator, and Class A or Class B speaker circuits. See DN-
60772.
C
D
, EIA-232 P
OMPATIBLE
EVICES
PRN-7: 80-column printer. See DN-60897.
VS4095/5: Printer, 40-column, 24 V. Mounted in external backbox.
See DN-3260.
DPI-232: Direct Panel Interface, specialized modem for extending
serial data links to remotely located FACPs and/or peripherals;
mount on NFS-320 chassis. See DN-6870.
C
D
, EIA-485 P
OMPATIBLE
EVICES
ACM-24AT: ONYX Series ACS annunciator – up to 96 points of
annunciation with Alarm or Active LED, Trouble LED, and switch per
circuit. Active/Alarm LEDs can be programmed (by powered-up
switch selection) by point to be red, green, or yellow; the Trouble
LED is always yellow. See DN-6862.
AEM-24AT: Same LED and switch capabilities as ACM-24AT,
expands the ACM-24AT to 48, 72, or 96 points. See DN-6862.
ACM-48A: ONYX Series ACS annunciator – up to 96 points of
annunciation with Alarm or Active LED per circuit. Active/Alarm
LEDs can be programmed (by powered-up switch selection) in
groups of 24 to be red, green, or yellow. Expandable to 96 points
with one AEM-48A. See DN-6862.
AEM-48A: Same LED capabilities as ACM-48A, expands the ACM-
48A to 96 points. See DN-6862.
ACM-8R: Remote Relay Module with eight Form-C contacts. Can be
located up to 6,000 ft. (1828.8 m) from panel on four wires. See DN-
3558.
FDU-80: Terminal mode. 80-character, backlit LCD display. Mounts
up to 6,000 ft. (1828.8 m) from panel. Up to 32 per FACP. See DN-
6820.
LCD2-80: Terminal and ACS mode. 80-character, backlit LCD dis-
play. Mounts up to 6,000 ft. (1828.8 m) from panel. Up to 32 per
FACP. See DN-60548.
LDM: Lamp Driver Modules LDM-32, LDM-E32, and LDM-R32;
remote custom driver modules. See DN-0551.
SCS: Smoke control stations SCS-8, SCE-8, with lamp drivers SCS-
8L, SCE-8L; eight (expandable to 16) circuits (HVAC only). See DN-
4818.
TM-4: Transmitter Module. Includes three reverse-polarity circuits
and one municipal box circuit; mount on NFS-320 chassis or
remotely. See DN-6860.
B
ATTERIES
ORTS
ORTS

Advertisement