Reference Manual
00809-0600-4410
3.5.3
Emerson 781S installation
A shielded twisted-pair cable is needed for connecting the Emerson 1410S and each 781S
Smart Antennas. Each antenna can be located up to 1312 ft. (400m) from the Gateway.
Figure 3-4: Emerson 1410S Gateway and Single 781S Smart Antenna
A. Emerson Wireless 1410S Gateway
B. Attach shield pair cable (Belden 3084A or equivalent)
C. Emerson Wireless 781S Smart Antenna
Figure 3-5: Emerson 1410S Gateway and Two 781S Smart Antennas
A. Emerson WirelessHART
B. Attach shield pair cable (Belden 3084A or equivalent)
C. Optional secondary Emerson Wireless 781S Smart Antenna
D. Tape back shield wire and foils
E. Emerson Wireless 1410S Gateway
Emerson 1410S/781S
Tape back shield wire and foils if connecting through a junction box between the
Emerson 781S and 1410S Gateway.
®
781S Smart Antenna
Installing the Gateway
September 2020
27