Specifications - Omron E5GC-600 Manual

Digital limit controllers
Table of Contents

Advertisement

Specifications

Ratings
Power supply voltage
Operating voltage range
Power consumption
Sensor input
Input impedance
Control method
Control
Relay output
output
Number of outputs
Auxiliary/
Limit
outputs
Output specifications
Number of inputs
Event
External contact input
input
specifications
Setting method
Indication method
Multi SP
Bank switching
Other functions
Ambient operating temperature
Ambient operating humidity
Storage temperature
Altitude
Recommended fuse
Installation environment
* Only four set points are selectable for event inputs.
A in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
85% to 110% of rated supply voltage
5.9 VA max. at 100 to 240 VAC, and 3.2 VA max. at 24 VAC or 1.8 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/
THB.)
ON/OFF control or 2-PID control (with auto-tuning)
SPST-NO, 250 VAC, 2 A (resistive load),
electrical life: 100,000 operations,
minimum applicable load: 5 V, 10 mA (reference value)
1 or 2 (depends on model)
SPST-NO relay outputs, 250 VAC, 2 A (resistive load),
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value)
1 (depends on model)
Contact input ON: 1 kΩ max., OFF: 100 kΩ min.
Non-contact input ON: Residual voltage 1.5 V max.; OFF: Leakage current 0.1 mA max.
Current flow: approx. 7 mA per contact
Digital setting using front panel keys
11-segment digital displays and individual indicators
Character height: PV: 10.5 mm, SV: 5.0 mm
Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations, or
serial communications.*
None
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, 40% AT,
100% AT, MV limiter, input digital filter, self tuning, robust tuning, PV input shift, run/stop, protection
functions, extraction of square root, logic operations, temperature status display, simple programming,
moving average of input val-ue, display brightness setting, and work bit message
−10 to 55°C (with no condensation or icing), For 3-year warranty: −10 to 50°C with standard mounting (with
no condensation or icing)
25% to 85%
−25 to 65°C (with no condensation or icing)
2,000 m max.
T2A, 250 VAC, time-lag, low-breaking capacity
Installation Category II, Pollution Degree 2 (IEC 61010-1 compliant)
E5GC-600
5
5