Press and hold the
Level key for three seconds. This will get the unit back to the Initial Setting level.
L
1. The first parameter in the initial setting level is the (in-t). This is the input type parameter use
the instruction sheet or user manual to determine the correct setting based on the input type is
applied to the unit for the application. Use the Up/Down arrow keys to adjust the value.
2. Tap on the
Mode key once to get to the next parameter (d-u). Select the units to be displayed
M
ether °C or °F. Use the Up/Down arrow keys to adjust the value.
3. Tap on the
Mode key once to get to the next parameter (sl-h). This is used to determine the
M
upper set point limit. Use the Up/Down arrow keys to adjust the value. The value set here will be
the highest value of the set point in the operation level.
4. Tap on the
Mode key once to get to the next parameter (sl-l). This is used to determine the
M
lower set point limit. Use the Up/Down arrow keys to adjust the value. The value set here will be
the lowest value of the set point in the operation level.
5. Tap on the
Mode key several times to get to the (alt1) parameter. This is used to determine if
M
the unit is set up for High Limit control (Heating) or Low Limit control (Cooling). Use the Up/Down
arrow keys to adjust the value. A selection of (2) will set the unit for High Limit control and a
selection of (3) will set the unit for Low Limit control.
6. Note: If the unit is equipped with more than 1 alarm and these are not being used by the
application setting additional alarms (alt2) and (alt3) to a value of (0) will disable these output
indications on the front display. To disable these tap on the
appear and adjust them using the Up/Down arrow keys to a value of (0).
7. Note: If the Event Input will be used to reset the alarm condition set this next parameter:
Tap on the
Mode key several times to get to the (ev-1) parameter. This needs to be changed
M
from (msp0) to (lat). Use the Up/Down arrow keys to adjust the value. This will reassign the
Event Input to Alarm Latch Cancel.
Press and hold the
Level key for three seconds. This will get the unit back to the Operation Setting
L
level.
At this point the controller is set up for commissioning:
1. Verify that the Process Value is reading correctly.
2. Tap on the
Mode key to get to
M
set to (0) the controller will add this value to the set value and may cause damage to the
system.
3. Tap on the
Mode key until the controller is reading the process value and set point.
M
High Limit Control testing:
If the set point is adjusted below the actual process value the SUB1 LED should be ON and the system
should not run. Raise the set point using the Up arrow key and set the high limit for the application. Verify
that the SUB1 LED is still ON and that the system cannot be started. Apply a reset to the Limit controller
via event input or PF key. The SUB1 LED should go off and the system should be able to be started.
M
(a
l-1) this must be set to a value of (0). If this is not
E5GC-600
Mode key until (alt2) and (alt3)