is changed in zenon Editor. Runtime can reload the changed files in the ongoing
operation, but system-related changes are excluded as they generally require Runtime
to be restarted.
The task bar has a button for selecting the display language, and shows the logged in
user and the current time and date. By clicking the Login/Logout button, it is possible
to change the currently registered user of the visualization. Depending on the project
settings, a customized logo can be displayed in the middle of the task bar. If a user with
administrator rights is logged in, the name of the computer on which the visualization
runs as well as the corresponding IP addresses of up to two Ethernet adapters are
displayed.

Single-line diagram pages

Depending on the project settings, up to 12 SLD pages can be created, containing the
plant-specific switchboards and bays. The pages' content is plant specific.
The automatic line coloring or topology coloring feature presents an immediate
overview of powered, unpowered, grounded and faulty parts of the electrical network
depending on the power status of the lines. Different colors can be selected for
representing the different voltage levels connected through a transformer. The
statuses of the lines are influenced by the status of the circuit breakers. Undefined or
faulty switches cause different coloring of the lines.
The calculated topological model can also be used for the interlocking of commands.
The topology engineering is handled while constructing the SLD in zenon Editor.
To allow screen-overlapping models, the entire topology design and configuration is
always project-wide. Therefore, a single topological model is defined per project,
which is used for the calculation of the circuit breaker or disconnector switch statuses
and ultimately for the coloring of the lines and transformers.

System diagnostic pages

Depending on the project settings, up to 12 system diagnostic pages are available
displaying the plant-specific network representations.