Installation, Operation
and Maintenace
Manual
Flygt ENM 10 Level regulator

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Flygt ENM 10 and is the answer not in the manual?

Questions and answers

Summary of Contents for Xylem Flygt ENM 10

  • Page 1 Installation, Operation and Maintenace Manual Flygt ENM 10 Level regulator...
  • Page 3: Table Of Contents

    Approvals............................. 7 Product Description..........................8 ................................8 Installation............................9 Level Regulator..........................10 Connection of Level Regulator for Audible or Visible Alarm............12 Ex Installation............................. 12 Maintenance............................13 Available languages..........................14 ................................14 Flygt ENM 10 Level regulator Installation, Operation and Maintenace Manual...
  • Page 4: Introduction

    • All service and repair work is done by Xylem-authorized personnel • Genuine Xylem parts are used • Only Ex-approved spare parts and accessories authorized by Xylem are used in Ex- approved products Flygt ENM 10 Level regulator Installation, Operation and Maintenace Manual...
  • Page 5 • Economic losses Warranty claim Xylem products are high-quality products with expected reliable operation and long life. However, should the need arise for a warranty claim, then contact your Xylem representative. Flygt ENM 10 Level regulator Installation, Operation and Maintenace Manual...
  • Page 6: Safety

    This includes any modification to the equipment or use of parts not provided by Xylem. If there is a question regarding the intended use of the equipment, please contact an Xylem representative before proceeding •...
  • Page 7: User Safety

    • Wash the skin with soap and water for at least one minute • Seek medical attention, if required Ex-approved products Follow these special handling instructions if you have an Ex-approved unit. Flygt ENM 10 Level regulator Installation, Operation and Maintenace Manual...
  • Page 8: Environmental Safety

    • Follow local laws and regulations regarding recycling if the unit or parts are accepted by an authorized recycling company • If the first guideline is not applicable, then return the unit or parts to your Xylem representative Waste and emissions regulations Observe these safety regulations regarding waste and emissions: •...
  • Page 9: Safety Data For Ex Approved Installation

    EN 60079-0:2009/IEC 60079-0:2007 EN 60079-11:2007/IEC 60079-0:2006 EN 60079-26:2007/IEC 60079-26:2006 Intrinsically safe circuits are required for the automatic control system. - Use a EX-safety barrier (e.g. Prod. no. 84 01 07). 0080 Flygt ENM 10 Level regulator Installation, Operation and Maintenace Manual...
  • Page 10: Product Description

    In many cases, local codes require that the regulator be connected to a low-voltage supply, even though it is approved for a higher voltage. Xylem recommends that the regulator be connected to a low-voltage supply, 48 or 24 V, and a protective transformer.
  • Page 11: Installation

    3. The pump stops when the lower level regulator returns to the vertical position. 4. The basin starts filling up again, and the process starts all over again. Installation Avoid damage the level regulator during installation Flygt ENM 10 Level regulator Installation, Operation and Maintenace Manual...
  • Page 12: Level Regulator

    Two regulators are used; one for starting and one for stopping. A third regulator can be connected if an alarm is required at a given level. Identical regulators can be used for all functions. Flygt ENM 10 Level regulator Installation, Operation and Maintenace Manual...
  • Page 13 EU, Grey EU, Brown US, Red US, White Connections for emptying a Insulate sump Connections for filling a Insulate tank Cable colors See table above to identify related cable colors. Flygt ENM 10 Level regulator Installation, Operation and Maintenace Manual...
  • Page 14: Connection Of Level Regulator For Audible Or Visible Alarm

    Insulate Alarm low level Insulate Ex Installation NOTICE: Intrinsically safe circuits are required for the automatic control system. EX-safety barrier (that is Prod. no. 84 01 07) must be installed! Flygt ENM 10 Level regulator Installation, Operation and Maintenace Manual...
  • Page 15: Maintenance

    If the unit is found to be damaged, replace it with a new one • For Ex-installations/Ex-ENM-10, also make absolutely sure that the Ex-barrier is operating correctly • - The LED changes when the switch is toggled Flygt ENM 10 Level regulator Installation, Operation and Maintenace Manual...
  • Page 16: Available Languages

    Ten podręcznik jest dostępny do pobrania w języku polskim z następującym adresem: Português Este manual também está disponível para download em Português, no seguinte endereço: Русский В книге также доступна для загрузки на русском языке по следующему адресу: Flygt ENM 10 Level regulator Installation, Operation and Maintenace Manual...
  • Page 17 Denna handbok finns också tillgänglig att ladda ned på svenska från följande adress: Български Настоящото ръководство е на разположение за сваляне на български от следния адрес: 中文 这本手册是在中国也可以从下面的下载地址: 한국의 이 책자는 또한 한국을 다운로드할 다음 주소입니다 : Flygt ENM 10 Level regulator Installation, Operation and Maintenace Manual...
  • Page 20 For more information on how Xylem can help you, go to xyleminc.com Xylem Water Solutions AB Visit our Web site for the latest version of this document and more information Gesällvägen 33...