1. General Description Please read through this operation manual before using and installation to avoid damage of the machine and personal injuries. SIC-R2 water chiller comprises of two series; water-cooled and air-cooled, both adopt single vapor compression circuit and equipped with compressor overload protection, pump overload protection, anti-phase and open phase alarm, anti-freeze protection, pressure controller which all ensure a stable and long-service-life performance.
1.1 Coding Principle 1.2 Main Features ● Cooling range 7~25 . ℃ ● Insulated water tank and evaporator made of stainless steel. ● Equipped with anti-freeze therostate. ● Adopt R410A refrigerant to improve coefficient of performance (COP) and R410A is ozone-friendly. ●...
Page 9
Chapter 7, which contains service instructions intended for service engineers. Other chapters contain instructions for the daily operator. Any modifications of the machine must be approved by SHINI in order to avoid personal injury and damage to machine. We shall not be liable for any damage caused by unauthorized change of the machine.
Safety Regulations The user must conform to the following safety rules when operating the machine. 1.4.1 Security Labels Attention! Installation of the device is allowed only to the professional electrician. Before maintaining and repairing the device, be sure to turn off the main switch and control switch.
1.4.2 Signs and Labels This is for indicating motor rotating direction. When phase reversal happens, the alarm sounds and indicator on control panel will indicate. Please exchange the place of the two electrical wires to solve this problem. Pump pressure gauge: display actual pressure of cold water system.
Shini (including employees and agents). Shini is exempted from liability for any costs, fees, claims and losses caused by reasons below: 1. Any careless or man-made installations, operation and maintenances upon machines without referring to the Manual prior to machine using.
2. Structural Features and Working Principle 2.1 Main Functions SIC-R2 water chiller is mainly made up of four components. They are compressor, condenser, thermostate expansion valve and evaporator. The machine uses single stage vapor compression refrigeration system and takes the advantage of the mechanism of transformation between gas and liquid for absorbing and releasing heat by using of refrigerant to achieve the effectiveness of refrigeration.
Page 20
Hot-air bypass function: the compressor continues working when process water is cooled down to required temperature, then the hot-air bypass valve opens as the temperature drops to its set value. A part of the refrigerant from the compressor passes through the by-pass valve and then reaches evaporator, balancing out part of the machine refrigerating capacity and then goes back to compressor without passing through the condenser.
Page 21
opens as the temperature drops to its set value. A part of the refrigerant from compressor passes through by-pass valve and then reaches evaporator, balancing out part of the machine refrigerating capacity and then goes back to compressor without passing through condenser. With the help of hot-air bypass valve, system can stay in balanced condition and meanwhile can keep control accuracy within ±1 .
2.2 Main Parts and Functions 2.2.1 Compressor 1) Compressing and conveying the refrigeration steam and forming low pressure in evaporator and high pressure in condenser, the compressor is the core of the whole system. 2) SIC-R2 adopts scroll compressor. Picture 2-3: Compressor 2.2.2 Condensor A.
Picture 2-5: Condenser 2.2.3 Drying Filter 1) The functions of the dry filter are: clean the impurity in the refrigerant, absorb the free moisture in the refrigerant, and prevent the narrow section (especially the valve port of the heat expansion valve) of the pipe from forming ice jam.
2.2.5 High and Low Pressure Switch 1) The high and low pressure switch are used to control the working pressure of the compressor suction port and outlet port. 2) The high pressure of switch is 40 bar, and the low pressure of switch is 5 bar. 3) Give an alarm when the pressure of the compressor outlet port is higher than 40 bar or the pressure of the compressor suction port is lower than 5 bar.
Through the liquid level indicator, the water level in the tank can be viewd. Please confirm the version number of the manual before you order to ensure the stock number and the parts are consistent. 2.3.2 Liquid Pipe Solenoid Valve Picture 2-10: Liquid Pipe Solenoid Valve 1) Liquid pipe solenoid valve is used to cut the refrigerant supply immediately after the machine stops to prevent the compressor freezing.
2.3.4 Flow Switch Picture 2-12: Flow Switch 1) Flow switch is adopted to detect whether the chilled water flow is sufficient. 2) Flow switch is installed on the water pipe between the evaporator and the water tank. 2.3.5 Medium or high pressure pumps Medium and high pressure pumps are optional to meet any pressure requirements.
3. Installation and Debugging Attention! Read this chapter before installation. Install the machine according to following steps! 3.1 Machine Location 1) Water chiller should be installed in an environment that has good ventilation, such as draughty area near the window. Ambient temperature should not be more than 43℃.
authorized by our company. We shall not be reliable for machine damages caused by unauthorized modification. Attention! Before connecting the machine with power supply, please make sure that main switch is turned off ! 3.3 Water connections A. Water-cooled Series Parts Name :...
B. Air-cooled Series Parts Name : 1. Water chiller 2. Chilled water inlet 3. Chilled water outlet 4. Water outfall 5. Water refill port 6. Cooling water pump 7. Cooling water circulation 8. Chilled water circulation 9. Mould Cooling 10. Cooling tank 12.
6) After the installation is completed, check if there are leakages in the circulation system. Cooling water circulation pipe should be covered with a layer of insulated material to avoid temperature increasing and water drops forming on the surface of circulation pipe. 7) This seires of models mainly use cooling tower’s circulation to cool down the water.
Application and Operation 4.1 Panel Diagram 4.2 Common Screens Commonly used screens include the main screen and the alarm screen. 1. Main Screen The system will enter the main screen after countdown, which displays as follows: 2. Alarm Screen In case of unit failure, the alarm screen is as follows: 31(49)
4.3 Quick Operation 1. Changing and Setting Temperature If the user parameter [Lock Temp.] is set to "No", the setting temperature can be modified directly in the main screen, with operation details as follows: Note: the setting temperature can also be modified in the user parameters. 2.
Startup 1) Open the main power switch. 2) Set the temperature of chilling water (if the temp. has already been set, omit this step). The minimum temperature of this series machine should be set as 7℃. 3) Press button to start the water pump. 4) Press button to start the compressor.
4.6 User Menu Press the button on the main screen to enter the User Menu, which includes five items as the table below: Menu Item Funtion Remark User Setting To set the user parameters To display the current operating Unit Status status of the unit Allowing the query of the last 10 Press...
4.6.3 Machine Set The machine set includes six items as the table below: Item Function Remark Language To set the display language. Chinese and English Backlight Time Setting range:0~255min 0: backlight is not turned off. Compr Use To query the cumulative operation time of Time the compressor To set baud rate, parity bit, stop bit and...
Trouble-shooting Table 5-1: Single Compressor Fault Test Conditions Troubleshooting Solution Compressor Test when the compressor pressure High button has pressed If the [LP Check Delay] is 0, test Stop compressor only when the compressor button Check if the input is consistent with Compressor pressure without affect other has pressed;If the...
Page 37
Table 5-2: Double Compressor Fault Test Conditions Troubleshooting Solution Compressor 1 Test when the compressor pressure high button has pressed If the [LP Check Delay] is 0, test Stop compressor 1 when the compressor button has Compressor 1 only without affect Check if the input is consistent pressed;If the pressure low...
Page 38
Table 5-3: Triple,Quadruple Compressor Fault Test Conditions Troubleshooting Solution Compressor 1 Test when the compressor button has pressure high pressed If the [LP Check Delay] is 0, test when the Stop compressor 1 only without Compressor 1 compressor button has pressed;If the Check if the input is consistent affect other equipments to pressure low...
Page 39
Fault Test Conditions Troubleshooting Solution Blower 1 fault Check if the blower 1 fault input (Only applicable Compressor 1 runs the test input is consistent with the switch for air-cooled setting. series) Blower 2 fault Check if the blower 2 fault input (Only applicable Compressor 2 runs the test input is consistent with the switch...
Page 43
Attention! All repair work should be done by qualified personnel only to avoid damage to the machine or personnel injury. In order to operate the machine rightly and safely, please caution the matter follows: 1) Do not turn off the main power switch to stop the machine, except emergency situation.
3) Please check periodicaly to prolong the life of the machine and prevent the safety accident to appear. 4) The operation and service of the machine should be done by qualified technician only. (Please take notice that the disassembly and the inspection of the machines are hazardous when the machines are running!) 6.1 Fill in the Refrigerant 1) Infuse the nitrogen with pressure maintaining for some time.
6.2 Components Maintenance 6.2.1 Condenser A. Water-cooled series SIC-W-R2 series water chiller adopts tube-in-shell condenser which may have incrustations piled up in the inner side of its heat pipe or sundries caused by bad water treatment. All these will influence the heat emission effect, so it is necessary to clean the condenser at fixed periods to ensure its good working performance.
6.2.2 Evaporator SIC-R2 series water chiller adopts tube-in-shell condenser which may have incrustations piled up in the inner side of its heat pipe or sundries caused by bad water treatment. All these will influence the heat emission effect, so it is necessary to clean the condenser at fixed periods to ensure its good working performance.
Page 47
Tube-in-shell Evaporator Cleaning: 1. Connect chilling water inlet/outlet of machine with hoses according to above picture. 2. Bactericide and water (according to purchased bactericide mixing requirement for specific proportion) proportional to solution and pour into the water tank of machine, then start-up pump cleaning of the machine. 3.
6.3 Maintenance Schedule About the Machine 6.3.1 Model Production date Voltage Ф V Frequency Total power 6.3.2 Check after Installation Check the pipes are all correctly connected. Check if there are leakages in the piping system. Check if there are breaks in welding joint. Electrical Installation Voltage: Fuse specification: 1 Phase...
6.3.6 Trimonthly Checking Check whether condenser is under blockage. 6.3.7 Half-yearly Checking Check and clean the condenser and evaporator. Check and clean the filter and expansion valve. Check system performance. Clean condenser. 6.3.8 Yearly Checking Check whether the contactor is normal. 6.3.9 3 year Checking PC board renewal.