Binary Inputs (BI), continued..
NPT NPA UNIT DESCRIPTION
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
The values marked in bold are default values
136 -
GPIO Terminal X30/2 0=FALSE , 1=TRUE
137 -
GPIO Terminal X30/1 0=FALSE , 1=TRUE
140 -
ECB Test mode
141 -
ECB Drive Mode
ECB Automatic By-
142 -
pass Mode
143 -
ECB Bypass mode
144 -
ECB Off Mode
ECB Motor running
145 -
from Bypass/Drive
146 -
ECB Overload Trip
ECB
M2
Contactor
147 -
Fault
ECB
M3
Contactor
148 -
Fault
ECB External Inter-
149 -
lock
ECB Manual Bypass
150 -
Override
MG.11.G1.02 - VLT
®
is a registered Danfoss trademark
PARAMETER NUM-
SELECTION
BER
16-60:8
16-60:9
1= ECB running in Test
31-10:0
mode
1= running in Drive mode 31-10:1
1= running in Automatic
31-10:2
Bypass mode
1= running in Bypass mode 31-10:3
1= ECB in Off mode
31-10:4
1= The motor is running
31-10:5
from Bypass or Drive
1= ECB has detected an
31-10:6
overload trip
1= M2 Contactor Fault de-
31-10:7
tected
1= M3 Contactor Fault de-
31-10:8
tected
1= External Interlock fault
31-10:9
detected
Manual bypass Override in-
31-10:10
put is true