6.2

Electrical characteristics

Table 6-1: Electrical characteristics
kVA
50
75
125
150
225
300
6.3

Environmental characteristics

The PDU has the capability of withstanding any combinations of environmental conditions listed below
without mechanical or electrical damage or degradation of operation.
Operating ambient temperature: 0 to 40° C
Non-operating and storage ambient temperature: -25 to 55° C
Noise level, Per NEMA ST-20:
<50dbA (up to 150kVA)
o
<55dbA (up to 300kVA)
o
Barometric pressure: At elevations up to 3300 feet above sea level
Equipment is designated for indoor use in a clean (dust-free), temperature and humidity-controlled
environment
Voltage
480
480
480
480
480
480
Full Load Amps
61
91
151
181
271
362
Power Distribution Unit│94-1100-00002874 A0 EN 71
Main Breaker Rating,
Frame
125 AMP
125 AMP
250 AMP
250 AMP
400 AMP
600 AMP