Cabling Requirements - Nice E.T. Systems Drive 300 Installer's Instructions

Low traffic 300kg slide gate operator

Advertisement

Before moun ng the operator ensure your cables and condui ng are in place to prevent any inconvenience at a later stage.
All household mains cabling and circuits need to be installed by a qualifi ed electrician and signed off by a registered electrician.
Allow for spare cabling in case of faulty cable & breakages (especially important when using low specifi ca on cable).
As automa on systems vibrate when in use, it is highly recommended that only mul -stranded, fl exible cables be used.
If installing an intercom, remember to allow for suffi cient cable cores for all the users of the system as per manufacturers cabling requirements.
The Drive 300 motor is designed to facilitate 1 x 20mm conduit going directly into its housing from below. If more cabling needs to be routed to the
motor, we suggest that a weatherproof electrical box be installed as a distribu on box. All of the circuits can then be extended to the distribu on
box and terminated there.
1.
Courtesy lights twin + earth 1.0mm back to motor housing and
isolator switch.
2.
Intercom gate sta on (check with intercom supplier for cable
specifi ca ons)
3.
(220Vac) - twin + earth: 2,5mm stranded (An all pole nega vely
biased isolator must be installed within 1,5m of the motor unit, in
circuit with the 220Vac supply)
4.
Safety infra-red beam RX power & switch. 4 cores 0,5mm stranded
back to motor housing.
5.
Safety infra-red beam TX power. 2 cores 0,5mm stranded back to
motor housing.
6.
Electric lock power. 2 cores 0,5mm stranded back to independent
lock power supply via motor housing.

Cabling requirements.

7.
Free exit loop 1.5mm silicone insulated single core fl exible stranded
cable back to loop detector that is typically installed in the motor
housing.
8.
From intercom internal equipment (check with intercom supplier
for specifi ca ons) + 5 cores 0,5mm stranded for status LED, BT and
Pedestrian triggers.
9.
Alarm monitoring circuit. 2 cores 0,5mm stranded back to motor
housing.
10.
Op onal plug in transformer for low traffi c sites (29Vac) - twin +
earth. Min 0,5mm stranded (1Amp)
11.
Lock power supply. Twin + earth 2,5mm stranded from isolator
switch.
8