Data Aire gForce Ultra Installation, Operation And Maintenance Manual page 61

Computer room air conditioner (crac) equipment
Hide thumbs Also See for gForce Ultra:
Table of Contents

Advertisement

Condensate Pan and Pump (if equipped)
___ Check for leaks
___ Check for debris
___ Inspect/check float operation
___ Check pump operation
Dry Cooler (if applicable)
___ Inspect coil/clean if required
___ Inspect motor/motor mounts
___ Inspect fan blade(s)
___ Check wiring
___ Inspect piping for leaks
Equipment Runtimes
Blower
Compressor #1
Compressor #2
Condenser
Reheat #1 (if equipped)
Reheat #2 (if equipped)
Reheat #3 (if equipped)
Humidifier (if equipped)
Dehumidification
Energy Saver (if equipped)
_______ Reset all to zero runtimes
MAINTENANCE/INSPECTION CHECKLIST
Air Cooled Condenser (if applicable)
___ Inspect coil/clean if required
___ Inspect motor/motor mounts
___ Inspect fan blade(s)
___ Check wiring
___ Inspect piping for leaks
Glycol Pump (if applicable)
___ Glycol leaks (pump area)
___ Pump operation
___ Auto air vent clean of mineral deposits
_______ hrs
_______ hrs
_______ hrs
_______ hrs
_______ hrs
_______ hrs
_______ hrs
_______ hrs
_______ hrs
_______ hrs
61