4 .2 .2
If the F10x is mounted in an outdoor location, use a suitable enclosure with a minimum
of IP54 ingress protection. A higher level of ingress protection rating will be necessary
if the working atmosphere is or can be corrosive or if the enclosure is subject to wet
or dusty environments.
4 .3
DIN-rail Mounting
The F10x is designed for mounting on 35mm x 7 .5mm T-section "top hat" DIN rail to
EN50022 and uses an integrated DIN-rail clamp to hold it onto the rail. If the DIN-rail
bussing system is to be used, the bussing connectors must first be attached to the
DIN-rail.
For vertical DIN Rail installations, we recommend using a DIN Rail clamp below the
F10x modules (see accessory PBUS03) to prevent the units from sliding on the DIN
Rail.
4 .3 .1
The F10x is mounted to the DIN-rail by hooking the side opposite the DIN-rail latch to
the DIN Rail. The device is then pivoted to fit on the DIN-rail. Then the latch is pushed
toward the DIN-rail and snaps in place holding the F10x firmly on the DIN-rail.
For applications using the DIN-rail bussing connectors, the DIN-rail bussing connector
must first be snapped onto the DIN Rail – see Figure 4a. The F10x is then installed
over the DIN-rail bussing connector making sure that it is properly lined up (Figure 4b).