Fieldbus power supply
Hide thumbs Also See for CROUSE-HINDS Series:

Advertisement

HAZARDOUS (CLASSIFIED) LOCATION
Class I, Division 2, Groups ABCD T4
Class I, Zone 2, IIC T4 (US only)
Ex nA nL IIC T4 (Canada only)
-40°C
Tamb
65°C
-40°C
Tamb
70°C (load
To be installed in an IP54 or better enclosure
Output to
Fieldbus
Devices (typ.)
** A Bus may be formed with optional components that are installed in the DIN Rail channel.
The 24VDC power is supplied to this Bus and connections 7-10 must not be used.
Part Numbers:
F101-P*, F102-P*, F104-P*
"*": S = Pluggable Screw Terminal Connectors
C = Pluggable Spring Clamp Connectors
Installation must be in accordance with the National Electrical Code (NFPA 70, Article 504),
ANSI/ISA-RP12.6, or the Canadian Electrical Code (CSA C22.1), as applicable.
INM F10x Rev 1
8
FM CONTROL DRAWINGS
400mA)
F10x Fieldbus Power Supply
Connection
to Fieldbus
Host (typ.)
1 2 3
+
S -
T
Terminator
Vmax = 24VDC (F101), 30VDC (F102), 14VDC (F104)
Imax = 580mA (F101), 580mA (F102), 290mA (F104)
WARNING - EXPLOSION HAZARD. DO NOT DISCONNECT
EQUIPMENT WHEN A FLAMMABLE OR COMBUSTIBLE
ATMOSPHERE IS PRESENT.
4 5 6
7 8 9 10
+
S -
+
-
+
-
-
+
DIN Rail Bus**
Optional 24VDC
Connection to
other units.
24VDC
+
Power
-
Supply
24VDC Power Supply
may be installed in the
Non-hazardous area.
Power Supplied to the unit
must be fused for 8A circuitry.
2221 Yew Street, Forest Grove, Oregon 97116 USA
Title:
CONTROL DRAWING FOR F10x Supplies
CONTROL DRAWING FOR F10x Supplies
CLASS I, DIV 2 (ZONE 2)
CLASS I, DIV 2 (ZONE 2)
H H A A Z Z A A R R D D O O U U S S L L O O C C A A T T I I O O N N S S
Approved By:
M M i i k k e e S S t t r r a a u u s s e e r r
D D r r a a w w i i n n g g N N u u m m b b e e r r : : 5 5 0 0 2 2 - - 5 5 3 3 1 1
D D a a t t e e : : 0 0 3 3 / / 5 5 / / 1 1 3 3
R R e e v v . . : : B B . . 0 0
9