Summary of Contents for Eaton CROUSE-HINDS Ex - d Series
Page 1
Betriebsanleitung CROUSE-HINDS Operating instructions SERIES Mode d’emploi Explosionsgeschützte Ex - d (e) Steuereinheit, Verteilung aus Leichtmetall GHG 64 Explosion-protected flameproof control station and distributions, Ex - d (e) Series: GHG 64 GHG 640 7004 P0001 D/GB (d)
Explosionsgeschützte Ex-d (e) Steuereinheit, Verteilung aus Leichtmetall GHG 64 Technische Daten 1.1 Ex-d Gehäuse ATEX EU-Baumusterprüfbescheinigung PTB 08 ATEX 1043 X Gerätekennzeichnung nach 2014/34/EU und Norm EN 60079-0 D II 2 G Ex d IIB T6/T5/T4 Gb D II 2 G Ex de IIB T.* Gb D II 2 G Ex d IIB+H2 T6/T5/T4 Gb D II 2 G Ex de IIB+H2 T.* Gb D II 2 G Ex de mb q ia/ib [ia/ib] IIB T6/T5/T4* Gb...
Explosionsgeschützte Ex-d (e) Steuereinheit, Verteilung aus Leichtmetall GHG 64 1.1.1 Verlustleistung Ex-d Gehäuse Maßbild Ex-d Gehäuse Verlustleistung Größe 40 °C 55 °C 60 °C 94 W 134 W 54 W 94 W 42 W 82 W 112 W 158 W 68 W 112 W 53 W...
Page 5
Explosionsgeschützte Ex-d (e) Steuereinheit, Verteilung aus Leichtmetall GHG 64 Maßbild 1.2.1.1 Haupt-/ Sicherheitsschalter GHG 64 .. (80 A) Gehäuse Gr. 80 A Bemessungsspannung 690 V, 50/60 Hz Bemessungsstrom 80 A Zulässige Kurzschlussvorsicherung bis UN 400 V bis UN 500 V bis UN 690 V 100 A/gG 100 A/gG...
Page 6
Explosionsgeschützte Ex-d (e) Steuereinheit, Verteilung aus Leichtmetall GHG 64 Maßbild 1.2.1.3 Haupt-/ Sicherheitsschalter GHG 64 .. (400 A) Gehäuse Gr. 400 A Bemessungsspannung 690 V, 50/60 Hz Bemessungsstrom 400 A Zulässige Kurzschlussvorsicherung bis UN 400 V bis UN 500 V bis UN 690 V 500 A/gG 500 A/gG...
Explosionsgeschützte Ex-d (e) Steuereinheit, Verteilung aus Leichtmetall GHG 64 Drucktaster 1.2.2 Betätigungselemente Gerätekennzeichnung nach 2014/34/EU: D II 2 G Explosionsschutz Ex d II C T6 / Ex ed ib II C T6 EG-Baumusterprüfbescheinigung PTB 06 ATEX 1009 U Bemessungsspannung bis max. 690 V Bemessungsstrom max.
Explosionsgeschützte Ex-d (e) Steuereinheit, Verteilung aus Leichtmetall GHG 64 Schalgtaster mit Drehentriegelung 1.2.2.5 Schlagtaster Drehentriegelung Schutzart nach EN/IEC 60529: IP 66 Gewicht 1 Kontaktblock 1 Kontakt ca. 0,118 kg 1 Kontaktblock 2 Kontakte ca. 0,126 kg 2 Kontaktblöcke 4 Kontakte ca.
Explosionsgeschützte Ex-d (e) Steuereinheit, Verteilung aus Leichtmetall GHG 64 Drehschalter 20 A 1.2.4 Drehschalter 20 A, 32 A, 40 A, 63 A Bemessungsspannung bis max. 690 V Max. Bemessungsstrom 20 A, 32 A, 40 A, 63 A Schutzart nach EN/IEC 60529 IP 66 Anschlussklemme 2 x 2,5 mm²...
Explosionsgeschützte Ex-d (e) Steuereinheit, Verteilung aus Leichtmetall GHG 64 Schlüsseldrehschalter 20 A 1.2.5 Schlüsseldrehschalter 20 A, 32 A, 40 A, 63 A Bemessungsspannung bis max. 690 V Max. Bemessungsstrom 20 A, 32 A, 40 A, 63 A Schutzart nach EN/IEC 60529 IP 65 Anschlussklemme 2 x 2,5 mm²...
Explosionsgeschützte Ex-d (e) Steuereinheit, Verteilung aus Leichtmetall GHG 64 Leistungsschalter Betätigungsvorsatz 1.2.6 Leistungsschalter, Leitungsschutzschalter Betätigungsvorsatz Schutzart nach EN/IEC 60529 IP 66 Gewicht 0,12 kg Signallampe 1.2.7 Signallampe Schutzart nach EN/IEC 60529 IP 66 Bemessungsspannung LED 12 V - 250 V AC/DC Lampenleistung ca.
Schraube oder mit einer runden Schau- Ex-e Anschlusskasten betreffen, dürfen nur von Cooper Crouse- scheibe d=90 mm (Mindestspaltlänge 6 – Edelstahl Hinds / EATON oder einer qualifizierten Gewindegänge im Eingriff) bestellt werden. – Stahlblech lackiert Elektrofachkraft in Übereinstimmung mit national geltenden Regeln durchgeführt Sind in den Geräten und Verteilungen...
Explosionsgeschützte Ex-d (e) Steuereinheit, Verteilung aus Leichtmetall GHG 64 Installation Öffnen der Gehäuse Bild 2 Gehäuse mit optionalem Vor Öffnen des Gehäuses sicherstellen, dass Scharnier öffnen Für das Errichten / Betreiben sind die relevanten keine explosive Umgebungsatmosphäre nationalen Vorschriften (z.B. Betr.Si.V, Gerätesi- vorhanden ist.
Selbstlockern gesichert ist. 4. Die Kontermutter mit geeignetem Werkzeug Alle nicht benutzten metrischen Cooper fest anziehen (Prüfdrehmoment 3,2 Nm). Crouse-Hinds / EATON Kunststoff-KLE sind mit dem bescheinigten Verschluss für diese a Bei übermäßigem Anziehen können die metrischen KLE zu verschließen.
Explosionsgeschützte Ex-d (e) Steuereinheit, Verteilung aus Leichtmetall GHG 64 Elektrischer Anschluss Bild 1 Betätigungselemente einschrauben a Der elektrische Anschluss des Betriebs- mittels darf nur durch Elektrofachpersonal >= 10 mm erfolgen. Thread M22 x 1,5 a Vor Anschluss der Geräte ist die Spannungsfreiheit sicherzustellen bzw.
Explosionsgeschützte Ex-d (e) Steuereinheit, Verteilung aus Leichtmetall GHG 64 Die Begrenzungsschnur nicht zwischen Die Spaltflächen säubern. Dabei keine scharf - Bild 5 Gehäuse mit optionalem Gehäuseoberteil und -Unterteil kantigen Werkzeuge verwenden. Die Spalt- Scharnier schließen flächen müssen glatt und unverkrazt sein. einklemmen.
Page 17
Explosion-protected, light alloy Ex-d (e) control stations and distributions, Series: GHG 64 Technical Data 1.1 Ex-d light alloy enclosure ATEX type examination certificate PTB 08 ATEX 1043 X Marking acc. to 2014/34/EU and standard EN 60079-0 D II 2 G Ex d IIB T6/T5/T4 Gb D II 2 G Ex de IIB T.* Gb D II 2 G Ex d IIB+H2 T6/T5/T4 Gb D II 2 G Ex de IIB+H2 T.* Gb...
Explosion-protected, light alloy Ex-d (e) control stations and distributions, Series: GHG 64 1.1.1 Permissible power loss Ex-d enclosure Dimension drawing Ex-d enclosure Permissible power loss Size 40 °C 55 °C 60 °C 94 W 134 W 54 W 94 W 42 W 82 W 112 W...
Page 19
Explosion-protected, light alloy Ex-d (e) control stations and distributions, Series: GHG 64 Dimension drawing 1.2.1.1 Safety switch GHG 64 .. (80 A) Enclosure Gr. 80 A Rated voltage 690 V, 50/60 Hz Rated current 80 A Perm. short circuit back-up fuse up to UN 400 V up to UN 500 V up to UN 690 V 100 A/gG 100 A/gG...
Page 20
Explosion-protected, light alloy Ex-d (e) control stations and distributions, Series: GHG 64 Dimension drawing 1.2.1.3 Safety switch GHG 64 .. (400 A) Enclosure Gr. 400 A Rated voltage 690 V, 50/60 Hz Rated current 400 A Perm. short circuit back-up fuse up to UN 400 V up to UN 500 V up to UN 690 V 500 A/gG 500 A/gG...
Explosion-protected, light alloy Ex-d (e) control stations and distributions, Series: GHG 64 Push button 1.2.2 Control elements Marking acc. to 2014/34/EU D II 2 G Explosion category Ex d II C T6 / Ex ed ib II C T6 EC type examination certificate PTB 06 ATEX 1009 U Rated voltage to max.
Explosion-protected, light alloy Ex-d (e) control stations and distributions, Series: GHG 64 Mushroom-head push button 1.2.2.5 Mushroom-head push button with twist release with twist release Degree of protection to IEC/EN 60529 IP 66 Weight 1 contact element 1 contact acc. 0.118 kg 1 contact element 2 contacts acc.
Explosion-protected, light alloy Ex-d (e) control stations and distributions, Series: GHG 64 Rotary switch 20 A 1.2.4 Rotary switch 20 A, 32 A, 40 A, 63 A Rated voltage up to max. 690 V Max. rated current 20 A, 32 A, 40 A, 63 A Degree of protection to IEC/EN 60529 IP 66 Terminal...
Explosion-protected, light alloy Ex-d (e) control stations and distributions, Series: GHG 64 Key-operated switch 20 A 1.2.5 Key-operated switch 20 A, 32 A, 40 A, 63 A Rated Voltage up to max. 690 V Max. Rated current 20 A, 32 A, 40 A, 63 A Degree of protection to IEC/EN 60529 IP 65 Terminal...
Explosion-protected, light alloy Ex-d (e) control stations and distributions, Series: GHG 64 Main current switch actuator unit 1.2.6 Main current switch actuator unit Degree of protection to IEC/EN 60529 IP 66 Weight 0.12 kg Signal lamp 1.2.7 Signal lamp Degree of protection to IEC/EN 60529 IP 66 Rated voltage LED 12 V - 250 V AC/DC...
IEC/EN 60529. may only be carried out by Cooper Crouse- – sheet steel, painted Hinds / EATON or by a qualified electrician in The enclosure cover can be ordered with a Additional information on the resistance of...
Messrs. the hinge until the hinge catch disengages. This upwards, downwards or sideways. Cooper Crouse-Hinds / EATON. prevents the enclosure cover from tipping to Suitable screws with a spring washer and one side. When opening the cover fully, care...
Any unused metric Cooper Crouse-Hinds / EATON moulded plastic cable entries shall be 4. Use a suitable tool to tighten the lock nut sealed with the blanking plug certified for these securely (test torque 3.2 Nm).
Explosion-protected, light alloy Ex-d (e) control stations and distributions, Series: GHG 64 Electrical connection Fig. 3 Screwing-in of actuator a The connection of equipment may only be carried out by qualified electricians. >= 10 mm a Prior to opening the enclosures, it is Thread M22 x 1,5 necessary to ensure that the voltage supply has been isolated or to take suitable...
Repairs that affect the explosion protection may only be carried out by Cooper Crouse- In addition, before being put into operation, the Hinds / EATON or a qualified electrician in Closing apparatus / Cover lock correct functioning of the apparatus and of the...
Technischer Anhang Technical annex D/GB 10.2 Anordnung von Bedienelementen im Gehäuseoberteil Arrangement of actuators in enclosure cover 10.2.1 Legende für Zeichnungen Legend for drawings Fläche für Bedienelemete Drilling area for actuators Raster für Schaltervorsätze Distance between centres for switch < 20 A, elements <...
Page 33
Technischer Anhang Technical annex D/GB 10.2 Anordnung von Bedienelementen im Gehäuseoberteil Arrangement of actuators in enclosure cover 10.2.3 Fläche für Bedienelemente Größe 2 210*320 Drilling area for actuators cover Size 2 210*320 M22 x 1,5 1poliger Automat 1 poliger Automat 2 poliger Fi 2poliger Fi 2poliger Automat...
Page 34
Technischer Anhang Technical annex D/GB 10.2 Anordnung von Bedienelementen im Gehäuseoberteil Arrangement of actuators in enclosure cover 10.2.5 Anordnung von Befehlsgebern, Leuchten, Schaltern und Automaten in den Ex-d Gehäusen der Größe Arrangement of push-buttons, signal lamps, switches, MCBs, RCBs in Ex-d enclosures 320 * 430 430 * 430 430 * 650...
Page 35
Technischer Anhang Technical annex D/GB 10.2 Anordnung von Bedienelementen im Gehäuseoberteil Arrangement of actuators in enclosure cover 10.2.6 Fläche für Bedienelemente Größe 6 320*430 Drilling surface enclosure cover Size 6 320*430 M22 x 1,5 10.2.7 Fläche für Bedienelemente Größe 8 430*430 Drilling surface enclosure cover Size 8 430*430 M22 x 1,5...
Page 36
Technischer Anhang Technical annex D/GB 10.2 Anordnung von Bedienelementen im Gehäuseoberteil Arrangement of actuators in enclosure cover 10.2.8 Fläche für Bedienelemente Größe 9 430*650 Drilling surface enclosure cover Size 9 430*650 M22 x 1,5 10.2.9 Fläche für Bedienelemente Größe 11 650*650 Drilling surface enclosure cover Size 11 650*650 M22 x 1,5...
Page 37
Technischer Anhang Technical annex D/GB Verdrahtungstabellen / Annex wiring tables Größe/Size 1 210 x 210 x 191 Größe/Size 2 210 x 320 x 191 Ø in mm² Ø in mm² I / A I / A Größe/Size 3 210 x 320 x 284 Größe/Size 4 320 x 320 x 191 Ø...
Technischer Anhang Technical annex D/GB Verdrahtungstabellen / Annex wiring tables Größe/Size 5 320 x 320 x 284 Ø in mm² I / A Verdrahtungstabellen / Annex wiring tables Größe/Size 6 320 x 430 x 191 Ø in mm² I / A...
Technischer Anhang Technical annex D/GB Verdrahtungstabellen / Annex wiring tables Größe/Size 7 320 x 430 x 284 Ø in mm² I / A Verdrahtungstabellen / Annex wiring tables Größe/Size 8 430 x 430 x 284 Ø in mm² I / A...
Page 40
Technischer Anhang Technical annex D/GB Verdrahtungstabellen / Annex wiring tables Größe/Size 9 430 x 650 x 284 Ø in mm² I / A Verdrahtungstabellen / Annex wiring tables Größe/Size 10 430 x 650 x 437 Ø in mm² I / A...
Technischer Anhang Technical annex D/GB Verdrahtungstabellen / Annex wiring tables Größe/Size 11 650 x 650 x 442 Ø in mm² I / A Beispiel für die Anzahl Example of the number of der verwendeten Leiter conductors used Leiter von außen 1,5 mm²...
Page 42
Technischer Anhang Technical annex D/GB 10.4 Verdrahtungstabellen Wiring tables Anmerkungen Note 1) max. Klemmenzahl in Abhängigkeit von 1) max. number of terminals depending on the obengenannter Gehäusetype und der above mentioned apparatus type and the eingebauten 2-Leiter-Klemme. built-in 2 wire terminals. 2) max.
Technischer Anhang Technical annex D/GB NPT Gewinde (EN 60079-1 Tabelle 4) NPT thread (EN 60079-1 table 4) min. min. 210x320 320x320 320x430 430x650 Wand- 210x210 210x320 320x320 320x430 430x430 430x650 650x650 Gewinde- hoch hoch hoch hoch Gewinde dicke Seite Seite Seite Seite Seite...
Page 44
Cooper Crouse-Hinds GmbH functionality. Their use in whatever form is subject to prior approval Neuer Weg-Nord 49 by Eaton. The same applies to Trademarks (especially Eaton, Moeller, 69412 Eberbach and Cutler-Hammer). The Terms and Conditions of Eaton apply, as E-Mail: Info-Ex@Eaton.com referenced on Eaton Internet pages and Eaton order confirmations.