Power Supply Specifications

HI (125/250 VDC)
HI (110/230 VAC)
a
Power consumption varies based on the device configuration. Each 10/100Base-Tx port consumes
roughly 1 W less than a fiber optic port.
b
The HI power supply is the same power supply for both AC and DC.
c
(T) denotes time-delay fuse. Internal fuse is not user-replaceable.
d
Rating at 85 °C (185 °F) ambient temperature at worst-case load.
5.2

Failsafe Relay Specifications

Maximum Switching Voltage
5.3

Operating Environment

The RUGGEDCOM MX5000 is rated to operate under the following environmental
conditions.
Ambient Operating
Temperature
Ambient Storage
Temperature
Ambient Relative
Humidity
Maximum Altitude
a
Measured from a 30 cm (12 in) radius surrounding the center of the enclosure.
RUGGEDCOM MX5000
Installation Manual, 01/2021, C79000-G8976-1059-13
Power
Supply Type
Min
b
88 VDC
b
85 VAC
30 VDC
125 VDC
125 VAC
220 VDC
250 VAC
-40 to 85 °C (-40 to 185 °F)
ab
-40 to 85 °C (-40 to 185 °F)
5% to 95%
c
2000 m (6562 ft)
Input Range
Max
300 VDC
264 VAC
Rated Switching Current
2 A, 60 W
0.24 A, 30 W
0.5 A, 62.5 W
0.24 A, 60 W
0.25 A, 62.5 W
Internal
Max. Power
Fuse Rating
Consumption
c
6.3 A, 250 V(T)
110 W
Isolation
1500 V
for 1 minute
rms
5
a
d
35

Advertisement

Table of Contents
loading