5 Plumbing Works

All plumbing work must be performed by
an authorised plumber.

5.1 technical Data for Water Batteries

Unit
Water battery-
connection
L30
R 1/2"
L40
R 1/2"
For further information, please refer to the special
estimation program for calculation of technical data
for the water battery (www.flexit.com).
3-way valve
Pump
Fig. 10 Recommended connection
Pipe
connection
cu Ø12
cu Ø12
Hot water from
boiler system
Throttle valve
Water battery in the
supply air system

5.2 Possible Valve types

3-way valve, type Honeywell, for capacity:
1.6 kvs art. no. 56232
2.5 kvs art. no. 57228
4.0 kvs art. no. 56283
2-way valve, type Honeywell, for capacity:
1.6 kvs art. no. 56432
2.5 kvs art. no. 56433
4.0 kvs art. no. 56434

5.3 Possible Valve Motor

It is necessary to use a valve motor that is controlled
by 0-10 V, where 10 V=100 % open.
Valve motor article number: 56234.

5.4 Connections

Before connecting the water battery, it
is necessary to check that the inspection
doors are accessible and there is space
enough to change the water battery.
Use the recommended connection (see Fig. 10) unless
specified otherwise. The water supply must be at the
bottom of the water battery - the return must be on
the top.
Place the adjustment valve as close to the unit as
possible. (Please note that many valve motors can go
in both directions and this can be set on the motor.
Set it so that the valve opens on an increasing 0-10 V
signal.)
If you use a water battery that has not had glycol
(or another antifreeze) added, the unit should be in
a heated room on account of the risk of frost in the
battery. Install air dampers with spring-loaded return
for outdoor air. Place the unit close to a gully to avoid
damage caused by any water leaks.
Install pipe routes to the water battery so that there is
free access to the motor and recovery system.
Remember vibration damping for water pipes.
You can see the location of pipes out of the unit in the
dimensioned drawings in Chap. 2.3.
Install the water battery so that there is
free access to the motor and exchanger
cassette.
Pipe routes for water pipes:
Remember vibration damping for water
pipes.
9