REBUILD KIT INSTRUCTIONS
5-Year Rebuild Kit Instructions for FireLock
Dry, Deluge, and Preaction Valves
SERIES 756 AND 758

REPLACING THE SHAFT SEAL IN THE CYLINDER

1.
Using a spanner wrench or similar device, remove the seal retainer
from the cylinder. NOTE: For smaller-size pistons, a spanner
wrench may need to be modified to fit into the holes of the seal
retainer.
2.
Remove the o-ring from the seal retainer. Save the o-ring for
re-installation.
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
REV_B
®
3.
Remove the shaft seal from the seal retainer. Discard the shaft
seal.
4.
Clean the area of the seal retainer where the shaft seal and o-ring
seat.
I-756/758.RBKIT