WARNING • Read and understand all instructions before attempting to install, remove, adjust, or perform maintenance on any Victaulic piping products. • Depressurize and drain piping systems before attempting to install, remove, adjust, or perform maintenance on any Victaulic piping products.
I-869E-3D / 869E-3D On-Off Deluge Valve / Installation, Maintenance, and Testing Manual HAZARD IDENTIFICATION 3. Wear safety glasses, hardhat, foot protection, and hearing protection. Wear hearing protection if you are exposed to long periods of Definitions for identifying the various hazard levels are provided below .
Page 5
I-869E-3D / 869E-3D On-Off Deluge Valve / Installation, Maintenance, and Testing Manual Hydraulic System Components Electric 1 Model 869E-3D Atmosphere 2 Accelerator/priming restrictor 3 Check valve 4 Priming strainer 5 Manual emergency release 6 Priming line ball valve 7 Hydraulic relay valve (HRV)
I-869E-3D / 869E-3D On-Off Deluge Valve / Installation, Maintenance, and Testing Manual INSTALLATION EQUIVALENT LENGTH Deluge valve equivalent length value (steel pipe), for use in hydraulically Subject to all other instructions, drawings and technical specifications calculated systems . that describe the 869E-3D deluge valve, install in their proper positions...
I-869E-3D / 869E-3D On-Off Deluge Valve / Installation, Maintenance, and Testing Manual OPERATION The 869E-3D deluge valve is suitable for systems that include electric fire detection, a piping system, and a wide variety of open nozzles . In the SET position, the line pressure, which is supplied to both the main valve control chamber (Figure 2, call out 1) and hydraulic relay valve (Figure...
I-869E-3D / 869E-3D On-Off Deluge Valve / Installation, Maintenance, and Testing Manual MAINTENANCE AND INSPECTION TESTS ANNUAL INSPECTION AND TEST CAUTION NOTICE • The system will be flooded. Take all necessary precautions to • Any activities that require taking the valve out of service may drain water and prevent damage in the area protected by the eliminate the fire protection provided.
I-869E-3D / 869E-3D On-Off Deluge Valve / Installation, Maintenance, and Testing Manual TROUBLESHOOTING DELUGE VALVE WILL NOT RESET Check for any of the following possible causes: NOTICE Closed priming line valve (Figure 2, call out 3) . Damaged deluge valve seat a foreign object is caught inside the •...