Summary of Contents for Victaulic FireLock NXT 769N Series
Page 1
WARNING • Read and understand all instructions before attempting to install, remove, adjust, or perform maintenance on any Victaulic piping products. • Depressurize and drain piping systems before attempting to install, remove, adjust, or perform maintenance on any Victaulic piping products.
Page 2
SERIES 769N FIRELOCK NXT ACTUATED VALVE ™ WITH DOUBLE-INTERLOCKED PNEUMATIC/ PNEUMATIC RELEASE PREACTION TRIM THIS QUICK REFERENCE SECTION IS FOR PLACING THE SYSTEM IN SERVICE AND FOR PERFORMING WATER FLOW ALARM TESTS. AN EXPERIENCED, TRAINED INSTALLER MUST READ AND UNDERSTAND THE FULL CONTENTS OF THIS MANUAL AND ALL WARNING MESSAGES BEFORE ATTEMPTING TO PLACE THE SYSTEM INTO SERVICE.
Page 3
NORMAL OPERATING POSITIONS FOR VALVES Valve Normal Operating Position Valve Normal Operating Position Water Supply Main Control Valve Open Pilot Line Fill Valve Closed – Restricted Fill Water Supply Main Drain Valve Closed System Line Shut-Off Valve Open System Main Drain Valve Closed System Line Fill Valve Closed –...
When an uninterrupted water flow alarm is required, Victaulic recommends the use of a low-pressure alarm NOTICE installed on the charge line downstream of the priming manifold •...
50 psi/345 kPa/3.4 Bar air pressure. Failure to follow this instruction could result in death or serious personal injury and property Install the valve assembly into the riser with two Victaulic rigid damage. couplings. Refer to the instructions, supplied with the coupling, for complete installation requirements.
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® TRIM COMPONENTS – EXPLODED VIEW DRAWING Series 769N FireLock NXT Actuated Valve - Double-Interlocked Pneumatic/Pneumatic Release Preaction Trim with Series 798 Pneumatic/Pneumatic Actuator When installing the optional Series 746-LPA Dry Accelerator, relocate the auto vent to the location of the indicated plug.
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® INTERNAL VALVE COMPONENTS – SECTION VIEW AND EXPLODED VIEW DRAWINGS Clapper Latch Diaphragm Assembly Clapper Seal Seat Exaggerated for Clarity Valve is shown in the “set” position The 1½-inch/48.3-mm and 2-inch/60.3-mm valve sizes contain washers under the heads of the cover plate bolts.
The “off” or “high” pressure setting should be 18 psi/124 kPa/1.2 Bar. When a base- or riser-mounted air compressor supplies air to a Series 769N FireLock NXT Actuated Valve, it is not necessary to install the Victaulic Series 757 Regulated Air Maintenance Trim Assembly (AMTA). In this case, the air line of the compressor connects to the trim at the fitting where the Series 757 Regulated AMTA is installed normally (refer to the applicable trim drawing).
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® SECTION I • Initial System Setup I-769N.Preaction/DPA_10 REV_A...
Page 11
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® INITIAL SYSTEM SETUP Step 6: NOTICE When pilot pressure reaches approximately 10 psi/69 kPa/0.7 Bar, pull up on the pilot chamber Auto Vent Sleeve, which is located on the air •...
Page 12
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® INITIAL SYSTEM SETUP (CONTINUED) Step 12: Step 17: Open the charge line ball valve. Allow water to flow through the auto Open the water supply main control valve fully.
Page 13
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® WARNING • It is critical for the pilot line and system line shut-off valves and fill valves to be in the proper operating orientations, as shown below.
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® SECTION II • Resetting the System I-769N.Preaction/DPA_14 REV_A...
Page 15
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® RESETTING THE SYSTEM Step 1: Step 5: Isolate the charge line ball valve by placing it in the closed position. Confirm that all system drains are shut and that the system is free from leaks.
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® SECTION III • Weekly External Inspection • Monthly External Inspection WARNING • The building owner or their representative is responsible for maintaining the fire protection system in proper operating condition.
Page 17
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® WEEKLY EXTERNAL INSPECTION MONTHLY EXTERNAL INSPECTION Record the system air pressure and water supply pressure. CAUTION Confirm that the water supply pressure is within the range of normal pressures observed in the area.
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® SECTION IV • Required Main Drain Test • Required Water Flow Alarm Test • Required Water Level and Low- Air Alarm Tests • Required Partial Operational Trip Test •...
Page 19
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® REQUIRED MAIN DRAIN TEST Perform the main drain test on a frequency required by the current 10. Compare the residual pressure reading, taken above, to the NFPA-25 code.
Page 20
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® REQUIRED WATER FLOW ALARM TEST Perform the water flow alarm test on a frequency required by the Open the water supply main drain valve fully to flush the water current NFPA-25 code.
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® REQUIRED WATER LEVEL AND LOW AIR ALARM TESTS FOR THE SYSTEM SUPERVISORY SWITCH Close the water supply main drain valve. Perform the water level and low air alarm tests for the system supervisory switch on a frequency required by the current NFPA-25 Close the water supply main control valve.
Page 22
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® REQUIRED WATER LEVEL AND LOW AIR ALARM TESTS FOR THE SYSTEM SUPERVISORY SWITCH (CONTINUED) 13. Open the water supply main drain valve. Valve Normal Operating Position...
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® REQUIRED WATER LEVEL AND LOW AIR ALARM TESTS FOR THE PILOT SUPERVISORY SWITCH Close the water supply main drain valve. Close the water supply main control valve.
Page 24
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® REQUIRED WATER LEVEL AND LOW AIR ALARM TESTS FOR THE PILOT SUPERVISORY SWITCH (CONTINUED) 13. Open the water supply main drain valve. Valve Normal Operating Position...
Remove pressure from the pilot line by pressing down on the Victaulic recommends performing the partial operational (trip) test screw of the pilot chamber Auto Vent Sleeve, which is located annually (at minimum).
/ Installation, Maintenance, and Testing Manual ® REQUIRED FULL OPERATIONAL TRIP TEST Victaulic recommends the full operational (trip) test every 3 years (at Record the following: minimum). NOTE: The frequency of the full operational (trip) test must 7a. The time between opening the remote system test valve be increased in the presence of contaminated water supplies, corrosive/ (inspector’s test connection) and operation of the actuated...
Page 27
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® This page intentionally left blank REV_A I-769N.Preaction/DPA_27...
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® SECTION V • Required Internal Inspection WARNING • Depressurize and drain the piping system before attempting to remove the cover plate from the valve. • The building owner or their representative is responsible for maintaining the fire protection system in proper operating condition.
Page 29
16. While the clapper is rotated out of the valve body, pull the latch forward to inspect the diaphragm. If the diaphragm shows any signs of wear or damage, replace it with a new, Victaulic-supplied diaphragm. Refer to the “Removing and Replacing the Diaphragm”...
Page 30
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® SECTION VI • Removing and Replacing the Clapper Seal • Removing and Replacing the Clapper Assembly • Installing the Cover Plate Gasket and Cover Plate •...
Pry the clapper seal, along with the seal ring, out of the clapper. Inspect the clapper seal. If the clapper seal is torn or worn, replace it with a new, Victaulic-supplied clapper seal. If replacing the clapper seal assembly with a new assembly, skip to step 7.
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® REQUIRED SEAL ASSEMBLY BOLT/BOLT SEAL TORQUES Nominal Size Required Torque inches or mm inch-lbs/N•m 1 ½ 2 ½ 76.1 mm 165.1 mm Install the clapper seal into the clapper carefully. Ensure that the seal ring snaps into the clapper completely.
Verify that the cover plate gasket is in good condition. If the gasket is torn or worn, replace it with a new, Victaulic-supplied gasket. Align the holes of the cover plate gasket with the holes in the cover plate.
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® REMOVING AND REPLACING THE DIAPHRAGM CAUTION Remove the system from service by following steps 1 – 11 of the • DO NOT over-tighten the cover plate bolts.
Failure to follow this instruction could cause improper valve operation, resulting in property damage. Use only a new, Victaulic-supplied filter. Install the new filter onto the filter adapter, as shown above. Make sure the o-ring is positioned on the filter adapter, as shown above.
I-769N.Preaction/DPA / Victaulic Series 769N FireLock NXT ™ / Installation, Maintenance, and Testing Manual ® SECTION VII • Troubleshooting I-769N.Preaction/DPA_36 REV_A...
Page 37
The Series 798 Pneumatic/Pneumatic Actuator has a broken seal. If the above procedure does not work, contact Victaulic. Water is leaking through the Series 798 Pneumatic/Pneumatic The air chamber of the Series 798 Pneumatic/Pneumatic Actuator is not set. Ensure that the auto vent seals of the Series 798 Pneumatic/Pneumatic Actuator.
Need help?
Do you have a question about the FireLock NXT 769N Series and is the answer not in the manual?
Questions and answers