TP482000B V300R002C03 Telecom Power
(TP482000B-N20B1, TP482000B-N20B2,
TP481200B-N20B1, and TP481200B-N20B2)
User Manual
No.
Check Item
3
Check whether all cables are
bound neatly.
4
Check whether the cabinet
ground bar is securely connected
to the site or equipment room
ground point.
5
Check whether ground cables are
rusty.
6
Check whether the DC RTN+
busbar is grounded.
7
Check whether cables are at
danger of overheating
deteriorating.
8
Check whether cables are
misshapen by metal parts.
9
Check whether cables pass
behind the air exhaust vents of
rectifiers.
10
Check whether power cables use
standard terminals.
11
Check whether cable insulation is
damaged.
Issue 07 (2020-04-10)
If...
Cables are not properly bound.
The cabinet ground bar is not
securely connected to the site or
equipment room ground point.
Cables have corroded after
being used for a long time.
The DC RTN+ busbar is not
properly grounded.
Cables are too thin.
Cables are not properly
routed.
Cables are not properly
installed.
Cables pass behind the air
exhaust vents of rectifiers.
Cables do not use stand
terminals.
Cable insulation is damaged.
Copyright © Huawei Technologies Co., Ltd.
6 Routine Maintenance
Then...
Bind cables neatly.
Connect the cabinet ground bar
to the site or equipment room
ground point.
Replace rusty cables.
Connect the ground cable to the
DC RTN+ busbar properly.
Replace the cables with
cables of the required
thickness.
Route the cables properly.
Replace the cables and route
them properly.
Reroute the cables to prevent
cable overheating.
Replace with standard terminals.
Reinsulate the cables with
insulation tape.