Heat Pump Advanced Feature Menu - Amana AVZC18 Installation & Service Reference

Heat pump unit
Hide thumbs Also See for AVZC18:
Table of Contents

Advertisement

H
P
A
EAT
UMP
DVANCED
SUBMENU ITEM
Clear Faults
Fault 1
Fault 2
Fault 3
Fault 4
Fault 5
Fault 6
SUBMENU ITEM
Time Stamp (TS)
Mode (MD)
Compressor Reduction Mode (CRM)
Requested and Actual % Demand
(RAD)
Requested and Reported ID CFM
(RAF)
Outdoor Air Temperature and Outdoor
Fan Status (ATOF)
Discharge Temperature and Outdoor
Coil Temperature (DCT)
Defrost sensor and Outdoor Liquid
Temperature (DLT)
Pressure Sensor and Suction
Temperature (PSDST)
F
M
EATURE
ENU
INDICATION/USER
MODIFIABLE OPTIONS
NO or YES
Most recent HP fault
2nd most recent HP fault
3rd most recent HP fault
4th most recent HP fault
5th most recent HP fault
6th most recent HP fault
COMMENTS
Provides compressor run time in hours.
Current system operation mode (COOLING, COOLING STARTUP, HEATING,
HEATING STARTUP, DEFROST, OIL RETURN, STOP).
Displays ON or OFF status. ON indicates that the reduction mode is operating and the
compressor is running at a lower speed than the cooling load would normally require.
Displays a 0-100% value, based on a ratio of the requested cooling demand to what the
system is actually providing.
Compares the requrested indoor airflow to what the indoor equipment has reported.
Displays the outdoor air temperature as well as the outdoor fan speed (TAP).
O: Off; 1: Low Tap; 2: Medium Tap; 3: High Tap
Displays the discharge temperature and outdoor coil temperature sensor readings.
Displays the defrost temperature sensor and outdoor liquid temperature sensor
reading.
Displays the pressure sensor reading which is taken slightly upstream of the suction
accumulator and outdoor suction temperature sensor reading.
DIAGNOSTICS
COMMENTS
Selecting "YES" clears the fault history.
STATUS
22