6-6-3. Applied Control of Outdoor Unit

Optional control P.C. boards provide access to a range of functions as listed below.
No.
Function
Power peak-cut Control
(Standard)
*Limit a maximum capacity
Power peak-cut Control
(Standard)
*Limit a maximum power
1
Power peak-cut Control
(For one input function)
*Limit a maximum capacity
Power peak-cut Control
(For one input function)
*Limit a maximum power
Power peak-cut Control
(Enhanced Function)
*Limit a maximum capacity
2
Power peak-cut Control
(Enhanced Function)
*Limit a maximum power
3
Snowfall Fan Control
External master ON/OFF
4
Control
Night operation
5
(Sound reduction) Control
Operation Mode Selection
Control
6
Operation Mode Selection
Control (forced choice)
7
Trouble/Operation output
Compressor Operation
8
Output
9
Operating Rate Output
To limit a maximum power, set the outdoor unit O.DN code to [009]=1, and set the criteria value of a maximum power consumption with
O.DN code [00A], [00B], [00C] and [00D]. Input the values for both cooling and heating.
Outdoor unit DN Code (O.DN) [00C], [00D]
Criteria value setting for a maximum cooling power
(e.g.) When the maximum standard value of cooling power consumption is set as 19.35 kW = 19.35kW
Outdoor unit DN Code (O.DN)
Value
Outdoor unit DN Code (O.DN) [00A], [00B]
Criteria value setting for a maximum heating power
(e.g.) When the maximum standard value of heating power consumption is set as 14.00 kW = 14.00kW
Outdoor unit DN Code (O.DN)
Value
Layout of Outdoor Unit Interface P.C. Board
* For Applicable controls, switch the DIP SW on the P.C. board or set the outdoor unit O.DN.
Outdoor unit for
Control P.C. board to be used
control P.C. board
TCB-
Connection
PCDM4E
PCMO4E
Header unit
Header unit
Header unit
Header unit
Header unit
Header unit
Header unit
Header unit
Header unit
Header unit
Header unit
Header unit
Individual
outdoor unit
Header unit
[00C]
[00D]
19
35
[00A]
[00B]
14
00
Outdoor unit interface P.C. board setting*
TCB-
TCB-
Connector
PCIN4E
No.
CN513
(blue)
CN513
(blue)
CN513
(blue)
CN513
(blue)
CN513
(blue)
CN513
(blue)
CN509
(black)
CN512
(blue)
CN508
(red)
CN510
(white)
CN510
(white)
CN511
(green)
CN514
(green)
CN514
(green)
- 90 -
DIP SW
Bit ON
Outdoor unit
No.
DN Code (O.DN)
[009]=0
(Factory default)
[009]=1
[009]=0
SW105
1
(Factory default)
SW105
1
[009]=1
[009]=0
SW105
2
(Factory default)
SW105
2
[009]=1
[008]=0
(Factory default)
[008]=1
[012]=0
(Factory default)
[012]=1