4-5-2. (1) Refrigerant Flow (Automatic emergency heating)

Header Unit (MMY-MUP2401*)
Fan
M
Fan motor
PMV1
Left side
Left side
Left side
TL1
Main heat exchanger
Main heat exchanger
Main heat exchanger
TE1
Leakage from PMV
Liquid-side service
valve = Full closure
Left side
Left side
Left side
Sub heat exchanger
Sub heat exchanger
Sub heat exchanger
PMV2
TE2
PMV3
TL2
TS3
High-pressure
sensor
SV3D
SV
Leakage from PMV
SV
Liquid-side service
valve = Full closure
SV41
TD1
Subcool
Heat Exchanger
PMV4
TL3
Check joint
Gas-side service valve
= Full open
TC2
TCJ
TC1
Heating
Trouble header outdoor unit
4-way valve
OFF
SV3D
OFF
PMV1
CLOSE
SV3F
OFF
PMV2
CLOSE
SV4(n)
OFF
PMV3
CLOSE
Outdoor fan
OFF
PMV4
CLOSE
Trouble
Fan
M
Fan motor
TO
Right side
Right side
Right side
Main heat exchanger
Main heat exchanger
Main heat exchanger
TG1
TG2
TG3
Right side
Right side
Right side
Sub heat exchanger
Sub heat exchanger
Sub heat exchanger
TE3
4-way valve
TS1
Low-pressure
sensor
Accumulator
SV3F
High-
High-
SV
pressure
pressure
switch
switch
SV42
TD2
TK1
TK2
TC2
TCJ
TC1
Heating
Temporal header outdoor unit
4-way valve
OFF
SV3D
Control
PMV1
Control
SV3F
Control
PMV2
Control
SV4(n)
Control
PMV3
Control
Outdoor fan
Control
PMV4
Control
The outdoor unit which communication line between indoor and outdoor is connected is the "Header unit".
Other outdoor units are called "Follower units".
Follower Unit (MMY-MUP1401*)
PMV1
TL1
PMV2
TL2
TS3
SV
SV41
Subcool
Heat Exchanger
PMV4
TL3
Check joint
TC2
TCJ
Heating
High-pressure gas refrigerant
Condensate liquid refrigerant
(38 HP system described in the example of (24 HP + 14 HP))
- 44 -
Set Up as Temporary
Header Unit during
Emergency Operation
Fan
M
Fan motor
TO
TG1
Main heat exchanger
Main heat exchanger
Main heat exchanger
TE1
TG2
Sub heat exchanger
Sub heat exchanger
Sub heat exchanger
TE2
High-pressure
sensor
Accumulator
SV3D
SV
SV3F
High-
pressure
switch
TD1
TK1
TC1
TC2
TCJ
Heating
Evaporative gas refrigerant (Low pressure)
Low-pressure circuit (Refrigerant recover line)
4-way valve
TS1
Low-pressure
sensor
TC1