Wireless remote controller

1
Turn on the power of the air conditioner.
When power is turned on for the first time
after installation, it takes approx. 5
minutes until the remote controller
becomes available. In the case of
subsequent power on, it takes approx. 1
minute until the remote controller
becomes available. Execute a test run
after the predetermined time has passed.
2
Push "ON/OFF" button on the remote
controller, select
[
with "MODE" button, and then select
[
HIGH ] with "FAN" button.
3

Cooling test run

Set the temperature to 17°C
with the temp. setup buttons.
4
Cooling test run
After confirming a signal
receiving sound "beep"
immediately set the
temperature to 18°C with the
temp. setup buttons.
5
Cooling test run
After confirming a signal
receiving sound "beep"
immediately set the
temperature to 17°C with the
temp. setup buttons.
6
Repeat procedures
Indicators "Operation" (green), "Timer"
(green), and "Ready" (orange) in the
wireless receiver section flash in approx.
10 seconds, and the air conditioner starts
operation. If any of these indicators does
not flash, repeat procedures 2 to 5.
7
Upon completion of the test run, push
"ON/OFF" button to stop operation.
Cool ] or [
Heat ]

Heating test run

Set the temperature to 30°C
with the temp. setup buttons.
Heating test run
After confirming a signal
receiving sound "beep"
immediately set the
temperature to 29°C with the
temp. setup buttons.
Heating test run
After confirming a signal
receiving sound "beep"
immediately set the
temperature to 30°C with the
temp. setup buttons.
4
5
4
5
.
<Overview of test run operations using the wireless
remote controller>
Cooling test run:
ON/OFF
17°C
18°C
17°C
Heating test run:
ON/OFF
30°C
29°C
30°C
Test operation from the outdoor unit
• Refer to "7-7-2. Function to Start/Stop (ON/OFF)
Indoor Unit from Outdoor Unit" in "7-7. Service
Support Function."
Note: The test operation returns to normal operating
mode after 60 minutes.
- 142 -
18°C
17°C
18°C
(test run)
ON/OFF
29°C
30°C
29°C
(test run)
ON/OFF
17°C
30°C