PS3031-2440-0000
Power supply 24 V DC, 40 A, 3-phase
2020-11-12 | Version: 1.0

Advertisement

Table of Contents
loading

Summary of Contents for Beckhoff PS3031-2440-0000

  • Page 1 Documentation | EN PS3031-2440-0000 Power supply 24 V DC, 40 A, 3-phase 2020-11-12 | Version: 1.0...
  • Page 3: Table Of Contents

    Parallel use to increase power ...................... 38 Inductive and capacitive loads...................... 38 4.10 Back-feeding loads .......................... 39 4.11 Use in a tightly sealed enclosure ..................... 39 4.12 Installation positions ........................ 39 5 Appendix .............................. 41 Accessories ............................. 41 Documentation issue status ...................... 41 Support and Service ........................ 42 PS3031-2440-0000 Version: 1.0...
  • Page 4 Table of contents Version: 1.0 PS3031-2440-0000...
  • Page 5: Overview

    • DC-OK relay contact • Shutdown input The PS3031-2440-0000 is a 3-phase 24 V power supply with an output current of 40 A and an output power of 960 W/1440 W. On the input side, the device features a wide-range input, active power factor correction (PFC) and inrush current limiting.
  • Page 6: Foreword

    , XFC , XTS and XPlanar are registered trademarks of and licensed by Beckhoff Automation GmbH. Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owners.
  • Page 7: Safety Instructions

    All the components are supplied in particular hardware and software configurations appropriate for the application. Modifications to hardware or software configurations other than those described in the documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG. Personnel qualification This description is only intended for trained specialists in control, automation and drive engineering who are familiar with the applicable national standards.
  • Page 8 Foreword Safety instructions and installation requirements for the PS3031-2440-0000 power supply DANGER Danger of electric shock, fire, injuries, injuries resulting in death! • Do not use the power supply without proper grounding (protective conductor). Use the terminal at the in- put terminal strip for the earth connection, not one of the screws on the housing.
  • Page 9: Terminology And Abbreviations

    Unless otherwise specified, AC 230 V parameters are valid at a mains frequency of 50 Hz. A keyword indicating a choice without implied preference. shall A keyword indicating a mandatory requirement. should A keyword indicating a choice with a clearly preferred method of implementation. PS3031-2440-0000 Version: 1.0...
  • Page 10: Technical Data, Mounting, Wiring

    500 mV 500 mV See Fig. Input voltage range; switch-on behavior defini- tions *) The power factor is the ratio of real (or active) power to apparent power in an AC circuit. Fig. 1: Input voltage range; switch-on behavior definitions Version: 1.0 PS3031-2440-0000...
  • Page 11: Dc Input

    1.5 A² s Start-up delay Typ. 500 ms 600 ms * The charge current of the interference suppression capacitors during the first few microseconds after switching on is not taken into account. Fig. 3: Typical switch-on behavior at nominal load, 25°C ambient temperature PS3031-2440-0000 Version: 1.0...
  • Page 12: Output

    Extra power is available repeatedly. Detailed information can be found in the chapter on Repeated pulse load [} 31]. If the power supply is subjected to extra power for longer than shown in the bonus time diagram (see Fig. Bonus time over output power [} 13]), the maximum output power is automatically reduced to 960 W. Version: 1.0 PS3031-2440-0000...
  • Page 13 Fig. 5: Dynamic overcurrent capability, typ. < 10 ms; Dynamic overcurrent capability, typ. < 25 ms Fig. 6: Bonus time over output power; Extra power recovery time Extra power is available as soon as the power is turned on and after an output short-circuit or output overload. PS3031-2440-0000 Version: 1.0...
  • Page 14 Technical data, mounting, wiring Fig. 7: Extra power after switching on; extra power after short circuit or overload Version: 1.0 PS3031-2440-0000...
  • Page 15: Hold-Up Time

    Characteristic curves and figures for operation on only two external conductors of a 3-phase system can be found in chapter Operation on two phases of a 3-phase system [} 35]. Fig. 8: Hold-up time over input voltage; switch-off behavior, definitions PS3031-2440-0000 Version: 1.0...
  • Page 16: Dc-Ok Relay Contact

    LED goes out when the set voltage is reached. ð This is an important condition to be considered especially if the load is a battery, the power sup- ply is used in parallel or the power supply is used for N+1 redundant systems. Version: 1.0 PS3031-2440-0000...
  • Page 17: Shutdown Input

    Fig. 11: Remote control of the output voltage; applying the control voltage Instructions: 1. Set the device to "Single Use" mode. 2. Set the output voltage (24-28 V) to the maximum required voltage. 3. Apply a control voltage to reduce the output voltage. PS3031-2440-0000 Version: 1.0...
  • Page 18: Efficiency And Losses

    75% of the nominal load for 25% of the time and 100% of the nominal load during the remaining time. Fig. 12: Efficiency over output current; losses over output current Fig. 13: Efficiency over input voltage; losses over input voltage Version: 1.0 PS3031-2440-0000...
  • Page 19 Please note the information in chapter Operation on two phases of a 3-phase system [} 35]! 2AC 400 V 2AC 480 V Efficiency Typ. 94.4% 94.7% At 24 V, 40 A Losses Typ. 56.9% 53.7% At 24 V, 40 A (full load) Fig. 14: Efficiency over output current at 24 V; losses over output current at 24 V PS3031-2440-0000 Version: 1.0...
  • Page 20: Lifetime Expectancy And Mtbf

    1,000,000 h means that statistically, if 10,000 devices are installed in the field, one device will fail every 100 hours. However, it is not possible to determine whether the failed device has run for 50,000 hours or only 100 hours. Version: 1.0 PS3031-2440-0000...
  • Page 21: Terminals And Wiring

    54 A. For higher currents please use a separate distribution terminal strip as shown in Fig. Using distribution terminals. Fig. 15: Series connection of outputs; use of distribution terminals PS3031-2440-0000 Version: 1.0...
  • Page 22: Functional Wiring Diagram

    Technical data, mounting, wiring 3.12 Functional wiring diagram Fig. 16: Functional wiring diagram Version: 1.0 PS3031-2440-0000...
  • Page 23: Front Side And Operating Elements

    Technical data, mounting, wiring 3.13 Front side and operating elements Fig. 17: PS3031-2440-0000, front Input terminals (screw terminals) Designation (A) Description L1, L2, L3 Mains input L1, L2, L3 PE input (protective conductor) Output terminals (screw terminals, two contact pins per pole)
  • Page 24 LED displays Overload LED DC-OK LED DC-OK contact Normal mode Closed During extra power Closed Overload (Vout < 90%) Open Short circuit at output Open Temperature switch-off flashes Open Shutdown input active flashes Open No input power Open Version: 1.0 PS3031-2440-0000...
  • Page 25: Emc

    Restrictions apply to residential, commercial and light industrial applications as well as to small businesses involving local DC networks according to EN 61000-6-3. No restrictions for all types of industrial applications. Tested with constant current loads, non-pulsating PS3031-2440-0000 Version: 1.0...
  • Page 26: Environment

    Characteristic curves and figures for operation on two phases of a 3-phase system can be found in chapter Operation on two phases of a 3-phase system [} 35]. Do not energize when condensation is present! Fig. 18: Output current over ambient temperature; output current over installation altitude Version: 1.0 PS3031-2440-0000...
  • Page 27: Protective Functions

    Typ. 0.45 mA / 0.91 mA At 3x 480 Vac, 60 Hz, TN, TT / IT network Max. 0.45 mA / 0.78 mA At 3x 440 Vac, 50 Hz, TN, TT / IT network Max. 0.60 mA / 1.20 mA At 3x 528 Vac, 60 Hz, TN, TT / IT network PS3031-2440-0000 Version: 1.0...
  • Page 28: Dielectric Strength

    This helps to avoid situations where a load starts unexpectedly or cannot be disconnected if an unnoticed earth leakage occurs. Version: 1.0 PS3031-2440-0000...
  • Page 29: Declaration Of Conformity And Approvals

    Technical data, mounting, wiring 3.19 Declaration of conformity and approvals EU declaration of conformity UL Certificate, UL508 Applicable for US and Canada PS3031-2440-0000 Version: 1.0...
  • Page 30: Dimensions And Weight

    The height of the DIN rail must be added to the depth of the device (127 mm) to calculate the total installation depth required. Housing material Housing: Aluminum alloy Cover: Steel Installation clearances See chapter on Safety instructions and installation requirements [} 8] Fig. 20: Front/side view of PS3031-2440-0000, all specifications in mm Version: 1.0 PS3031-2440-0000...
  • Page 31: Application Notes

    Fig. 21: Repeated pulse loads, definitions; Max. duty cycle curve Base load (W) Pulse load (over 100%) PEAK Duration between pulses (s) Pulse duration (s) PEAK Calculation: Duty cycle = T / (T PEAK PEAK = (T - (DutyCycle x T )) / DutyCycle PEAK PEAK PS3031-2440-0000 Version: 1.0...
  • Page 32 )) / DutyCycle = (1 s - (0.37 x 1 s)) / 0.37 = 1.7 s PEAK PEAK Further examples of pulse load tolerance PEAK PEAK 1440 W 960 W 1 s >25 s 1440 W 0 W 1 s >1.3 s 1200 W 480 W 1 s > 0.75 s 1440 W 480 W 0.1 s >0.16 s 1440 W 480 W 1 s >1.6 s 1440 W 480 W 3 s >4.9 s Version: 1.0 PS3031-2440-0000...
  • Page 33: Peak Current Capability

    Peak current voltage drops Typically from 24 V to 20 V At 80 A for 50 ms, ohmic load Typically from 24 V to 12 V At 200 A for 2 ms, ohmic load Typically from 24 V to 12 V At 200 A for 5 ms, ohmic load PS3031-2440-0000 Version: 1.0...
  • Page 34: External Input Protection

    If an external fuse is required or used, minimum requirements must be taken into account to avoid false tripping of the circuit breaker. • A circuit breaker with a minimum value of 6 A with B or C characteristic should be used. Version: 1.0 PS3031-2440-0000...
  • Page 35: Operation On Two Phases Of A 3-Phase System

    • This kind of operation is not covered by the UL approval. Additional testing may be required if the complete system has to be approved according to UL 508 or UL 60950-1. Fig. 24: When using only two phases: Permissible output current; hold-up time Fig. 25: Efficiency over output current at 24 V; losses over output current at 24 V PS3031-2440-0000 Version: 1.0...
  • Page 36: Output Circuit Breakers

    10 m 13 m 21 m 32 m B-16A 8 m 11 m 14 m 24 m B-20A 4 m 6 m 8 m 14 m Don't forget to double the distance to the load (or the cable length) when calculating the total cable length (plus and minus cable). Version: 1.0 PS3031-2440-0000...
  • Page 37: Charging Batteries

    • Power supplies connected in series should only be used in the standard installation position (terminals on the underside of the device). • Note that leakage current, electromagnetic interference, input inrush current, and harmonics increase when using multiple power supplies. Fig. 27: Series connection PS3031-2440-0000 Version: 1.0...
  • Page 38: Parallel Use To Increase Power

    • Note that leakage current, electromagnetic interference, input inrush current, and harmonics increase when using multiple power supplies. Fig. 28: Parallel connection Inductive and capacitive loads The device is designed to supply all load types, including capacitive and inductive loads. Version: 1.0 PS3031-2440-0000...
  • Page 39: Back-Feeding Loads

    The extent of the reduction influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous operation are provided below: Curve A1: Recommended output current. Curve A2: Max. permissible output current (results in about half the lifetime expectancy of A1). PS3031-2440-0000 Version: 1.0...
  • Page 40 Application notes Fig. 29: Installation position A (standard installation position) Fig. 30: Installation position B (upside down) Fig. 31: Installation position C (table mounting) Fig. 32: Installation position D (horizontal clockwise) Fig. 33: Installation position E (horizontal counterclockwise) Version: 1.0 PS3031-2440-0000...
  • Page 41: Appendix

    This bracket is used to mount the devices to a wall or panel without using a DIN rail. Fig. 34: ZS5301-0002, isometric view Documentation issue status Version Comment • First release • Corrections • Preliminary documentation for PS3031-2440-0000 PS3031-2440-0000 Version: 1.0...
  • Page 42: Support And Service

    Please contact your Beckhoff branch office or representative for local support and service on Beckhoff products! The addresses of Beckhoff's branch offices and representatives round the world can be found on her internet pages: https://www.beckhoff.com/english/beckhoff/world.htm You will also find further documentation for Beckhoff components there.
  • Page 44 More Information: www.beckhoff.com/ps3031-2440-0000 Beckhoff Automation GmbH & Co. KG Hülshorstweg 20 33415 Verl Germany Phone: +49 5246 9630 info@beckhoff.com www.beckhoff.com...

Table of Contents