Voltage and Frequency Limits and Trip Times

All models of the SOLECTRIA XGI 1000 comply with IEEE1547a-2014 requirements. The tables below show its standard
settings.
VOLTAGE RANGE
V < 45%
45% <= V < 60%
60% <= V < 88%
88% <= V < 110%
110% <= V <= 120%
V > 120%
FREQUENCY RANGE
F < 57 HZ
57 HZ <= F < 59.5 HZ
59.5 HZ <= F < 60.5 HZ
60.5 HZ <= F <= 62 HZ
V > 62 HZ
DOCR-070733-F (2/22/2021)
Table 11-2 Default Voltage Limits and Trip Times
VOLTAGE SETPOINT
V = 45%
V = 60%
V = 88%
N/A
V = 110%
V = 120%
Table 11-3 Frequency Limits and Trip Times
FREQUENCY SETPOINT
F = 57 Hz
F = 59.5 Hz
N/A
F = 60.5 Hz
F = 62 Hz
Figure 11-1 Derating with AC Voltage
CLEARING TIME
0.16 s
1.0 s
2.0 s
No trip
1.0 s
0.16 s
TRIP TIME
0.16 s
2.0 s
No trip
2.0 s
0.16 s
Page 72 of 78