9. Error indication

Error nr
Description
1
battery temperature
too high
2
battery voltage too
high
3, 4, 5
temp. sense error
6, 7, 8, 9
voltage sense error
17
charger temperature
too high
18
Internal error
20
charger bulk time
expired
24
Fan failure
34
Internal error
37
No input voltage
(only for the three
output version)
65
charger disappeared
during operation
66
Incompatible device
67
BMS connection lost
113, 114
Internal error
115
116, 117,
Internal error
118
119
Settings invalid
Page 17
Skylla-IP65
Possible cause
Overcharging or fast charging
Wiring mistake, or another charger
is over charging
Wiring mistake or temperature
sensor broken
Wiring mistake
The heat generated by the charger
cannot be removed
After 10 hours of bulk charging, the
battery voltage has still not reached
the absorption voltage.
This error indicates that the fan is
powered on but the circuit does not
measure any current draw by the
fan. Most likely the fan is either
broken or obstructed.
Mains removed or ac-input fuse
blown
One of the other chargers with which
this charger was synchronizing has
disappeared during operation
The charger is being paralleled to
another charger that has different
settings and/or a different charge
algorithm
Connection to the BMS lost
Communication error
Solution
Check air flow near the battery Improve
cooling of environment. The charger
stops automatically and will resume once
the battery has cooled down
Check all charging equipment.
Check cables and connections
Check the temperature sensor wiring and
if that doesn't help replace the
temperature sensor
Check the voltage sensor wiring.
Check air flow of the cabinet.
Improve cooling of environment.
The charger stops automatically and will
resume once the charger has cooled
down.
Contact your dealer
Possible cell failure or higher charge
current needed.
Contact your dealer
Contact your dealer
Check mains availability and fuse.
To clear the error, switch the charger off
and back on.
Make sure all settings are the same and
update firmware on all chargers to the
latest version.
Check the VE.Can bus cabling. When the
charger needs to operate in standalone
mode again, go to the setup menu #31
(BMS Present) and set to N.
Contact your dealer
Check wiring and terminators
Contact your dealer
Restore defaults in the setup menu #62.