17
|
Electrical installation
Installer and user reference guide
98
S1S
Factory-equipped operation switch:
OFF: Unit operation turned OFF
ON: Unit operation turned ON
Remote: Unit controlled (ON/OFF) with remote operation switch
Wiring remote operation switch:
Wiring
Maximum wiring length
Details – Remote low noise switch:
NOTICE
Low noise switch. If you want to remotely turn ON/OFF low noise operation, you
must install a low noise switch. Use a voltage-free contact for microcurrent (≤1 mA,
12 V DC).
Low noise switch
OFF
ON
Wiring low noise switch:
Wiring
Maximum wiring length
OFF
S1S
Normal mode
Low noise mode
Sheathed cable (2 wires)
Vinyl cords
0.75~1.25 mm²
130 m
Mode
Sheathed cable (2 wires)
Vinyl cords
0.75~1.25 mm²
130 m
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit
4P605460-1 – 2020.08