Daikin CO2 Conveni-pack LRYEN10A7Y1 Installer And User Reference Manual page 57

Outdoor unit
Hide thumbs Also See for CO2 Conveni-pack LRYEN10A7Y1:
Table of Contents

Advertisement

LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit
4P605460-1 – 2020.08
Example: Total refrigerant change in the system is 45  kg and room volume is
3
300 m
. 45/300=0.15, which is >RCL (0.072) and <QLAV (0.18), therefore install at
least 2 appropriate measures in the room.
70
65
a
60
55
50
45
40
35
30
25
20
15
10
5
0
0
50
100 150
200 250 300 350
  15‒2 Example graph for calculation
A
Refrigerant charge limit
B
Room volume
a
Installation is not allowed
b
2 appropriate measures required
c
1 appropriate measure required
d
No measure required
INFORMATION
Even if there is no refrigerating system on the lowest floor, where the largest system
charge (kg) in the building divided by total volume of the lowest floor (m
value for QLMV, provide a mechanical ventilation in accordance with EN 378-3:2016.
Space volume calculation
Take into account following requirements for the space volume calculation:
The space considered is any space that contains refrigerant-containing parts or
into which refrigerant can be released.
Use the room volume of the smallest, enclosed, occupied space to determine the
refrigerant quantity limits.
Multiple spaces that have appropriate openings (which cannot be closed)
between the individual spaces or are connected with a common ventilation
supply, return or exhaust system not containing the evaporator or the condenser
shall be treated as a single space.
Where the evaporator or condenser is located in an air supply duct system
serving multiple spaces, the volume of the smallest single space shall be used.
If the airflow to a space cannot be reduced to less than 10% of the maximum
airflow using an airflow reducer, then that space shall be included in the volume
of the smallest human occupied space.
For refrigerants of safety class A1, the total volume of all the rooms cooled or
heated by air from one system is used as the volume for calculation, if the air
supply to each room cannot be restricted below 25% of its full supply.
For refrigerants of safety class A1, the effect of the air changes may be
considered in calculating the volume if the space has a mechanical ventilation
system which will be operating during the occupation of the space.
Where the evaporator or condenser is located in an air supply duct system and
the system serves a non-partitioned multi-storey building, the occupied volume
of the smallest occupied storey of the building shall be used.
QLAV
b
c
400
450
500
550
600 650 700 750 800 850 900 950 1000
B (m³)
15
Unit installation
|
QLMV
RCL
d
3
) exceed the
Installer and user reference guide
57