Access category
Supervised access
Authorized access
  15‒2 Description of location classification
Location classification
Class I
Mechanical equipment
located within the occupied
space
Class II
Compressors in machinery
room or open air
Class III
Machinery room or open air If all refrigerant-containing parts are located in a machinery room or
Class IV
Ventilated enclosure
Appropriate measures
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit
4P605460-1 – 2020.08
Description
Rooms, parts of buildings, buildings
where only a limited number of people
may be assembled, some being
necessarily acquainted with the general
safety precautions of the location.
Rooms, parts of buildings, buildings
where only authorized persons have
access, who are acquainted with
general and special safety precautions
of the location and where
manufacturing, processing or storage of
material or products take place.
Description
If the refrigerating system or refrigerant-containing parts are located
in the occupied space, the system is considered to be of class I, unless
the system complies with the requirements of class II.
If all compressors and pressure vessels are either located in a
machinery room or in the open air, the requirements for a class II
location shall apply, unless the system complies with the
requirements of class III. Coils and pipework including valves may be
located in an occupied space.
in the open air, the requirements for a class III location shall apply.
The machinery room shall fulfil the requirements of EN 378-3.
If all refrigerant-containing parts are located in a ventilated
enclosure, the requirements for a class IV location shall apply. The
ventilated enclosure shall fulfil the requirements of EN 378-2 and EN
378-3.
INFORMATION
Appropriate measures are field supply. Choose and install all required appropriate
measures in accordance with EN 378-3:2016.
(natural or mechanical) ventilation
safety shut-off valves
safety alarm, in combination with a CO
alone is NOT considered an appropriate measure where occupants are restricted
in their movements)
CO
refrigerant leak detector
2
WARNING
Install the unit only in locations where the doors of the occupied space are not tight
fitting.
15
Examples
Business or professional offices, laboratories,
places for general manufacturing and where
people work.
Manufacturing facilities, e.g. for chemicals,
food, beverage, ice, ice cream, refineries,
cold stores, dairies, abattoirs, non-public
areas in supermarkets.
refrigerant leak detector (a safety alarm
2
Unit installation
|
Installer and user reference guide
55