LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit
4P605460-1 – 2020.08
WARNING
Use K65 piping for high-pressure applications with a working pressure of 120 bar
or 90 bar, depending on its location in the system.
Use K65 unions and fittings approved for a working pressure of 120 bar or 90 bar,
depending on its location in the system.
Only brazing is allowed for connection of pipes. No other types of connections are
allowed.
Expanding of pipes is not allowed.
NOTICE
Piping outside a machinery room or enclosure shall be protected against possible
accidental damage.
NOTICE
Refrigerant piping shall be protected or enclosed to avoid damage.
NOTICE
Refrigerant piping passing through fire resistant walls and ceilings shall be sealed in
such a way as to be consistent with the fire rating of the partition.
NOTICE
Piping shall be suitably supported according to its size and service weight. For more
information, see European Standard EN 378.
INFORMATION
To complete the refrigerating system, additional charging of refrigerant is required.
See
"18 Charging
Electrical installation (see
WARNING
If the power supply has a missing or wrong N-phase, equipment might break
down.
Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shock.
Install the required fuses or circuit breakers.
Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
Do NOT use taped wires, stranded conductor wires, extension cords, or
connections from a star system. They can cause overheating, electrical shock or
fire.
Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause
accidents.
3
Specific installer safety instructions
|
4
refrigerant" [
 101].
"17 Electrical
installation" [
4
 88])
Installer and user reference guide
15