This menu is only displayed if a CO2 sensor has been installed.
ATTENTION
CO
A CO2 sensor is not a standard part of all units, but may be purchased as an accessory.
2
If the number of people using a building varies considerably, controlling ventilation through the CO2
level in the extract air may be a good solution. This function is often used in offices and schools where
use varies greatly during the day and during the week.

CO2

↳ Vent.high CO2 level
↳ High CO2 level
↳ Normal CO2 level
20
Settings:
Standard setting:
Description:
Settings:
Standard setting:
Description:
Settings:
Standard setting:
Description:
sensor.
2
Level 2 / Level 3 / Level 4 / Off
Level 3
Here you indicate the fan speed level at which the unit
is to operate at high CO
level.
2
650 ↔ 2500 ppm
800 ppm
Here you indicate the CO
level at which the unit is to
2
switch to high fan speed level.
400 ↔ 750 ppm
600 ppm
Here you indicate the CO
- level at which the unit is to
2
switch to normal control.
2