[ IX Troubleshooting ]
Problem
The unit is in
Supply-water tempera-
operation, but the
ture on the secondary
secondary circuit
side is high.
water is not
correct.
(when the sec-
ondary-side con-
trol is enabled)
Supply-water tempera-
ture on the secondary
side is low.
The unit is mak-
The compressor is
ing a great deal of
being flooded.
vibrations and
noise.
HWE1517A
Check item
The difference be-
Water flow shortage on the secondary-
tween the supply-water
side pump
temperature on the pri-
mary side and the sec-
ondary side is too
small.
The difference be-
Excess water flow on the secondary-
tween the supply-water
side pump
temperature on the pri-
mary side and the sec-
ondary side is too
Secondary-side flow sensor fault
large.
Error code 2616 (1)
Capacity drop of the heat exchanger
was detected.
Error code 2616 (2)
Capacity shortage of the heat exchang-
was detected.
er
LEV fault in the main circuit
- 128 -
Cause
Reconfigure the system to increase the
maximum flow rate on the secondary-side
circuit. (e.g., Change the pump.)
Reconfigure the system to decrease the
minimum flow rate on the secondary-side
circuit. (e.g., Change the pump.)
Check the flow sensor and replace as nec-
essary.
Service or replace the heat exchanger.
Replace the heat exchanger.
Replace the LEV.
Solution