[ VIII Test Run Mode ]

[3] Refrigerant

Unit type
Refrigerant type
Refrigerant charge

[4] Standard operating characteristics (Reference data)

Reference data
Ambient
temperature
Temperature
Air-side heat exchanger inlet
Outlet water temperature
Pressure
LEV opening
Compressor
Fan
HWE1517A
QAHV-N560YA-HPB
R744
6.5kg
Operating condition
DB
WB
Discharge refrigerant
Suction refrigerant
Shell temperature
Outside temperature
Inlet water temperature
High pressure
Low pressure
Main circuit
Injection
Frequency
Frequency
Unit
1
°C
7
°C
6
°C
90
°C
7
°C
18
°C
2
°C
7
°C
9
°C
65
MPa
9.5
MPa
3.2
pulse
170
pulse
60
Hz
78
rpm
650
- 118 -
2
16
12.4
92
8
20
6
16
17
65
10
3.7
180
60
73
540
GB